Skip to main content
Siemens 6AG1135-6HD00-7BA1 — PLCs (Programmable Logic Controllers)

Siemens 6AG1135-6HD00-7BA1 Analog Output, 4 AO, 15/16 bit

MPN6AG1135-6HD00-7BA1
Active

Siemens 6AG1135-6HD00-7BA1, S7-1500 analog output module, 4 analog outputs, 15/16 bit resolution, 15 mm width, 58 mm depth.

$278.13Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1135-6HD00-7BA1 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)1.5 W
6AG1135-6HD00-7BA1 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)70 °C; = Tmax; > +60 °C max. 2x ±10 V permissible
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1135-6HD00-7BA1 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)31 g

Product details

Module at a Glance

The Siemens 6AG1135-6HD00-7BA1 is a 4-channel analog output module delivering voltage and current signals with resolution up to 16 bit including sign for ±10 V ranges, 15 bit for 0–10 V and 0–20 mA, and 14 bit for 4–20 mA. Above +60 °C the module derates to a maximum of 2 outputs for ±10 V. Each channel can be configured independently for voltage (0–10 V, ±10 V, 1–5 V, ±5 V) or current (0–20 mA, 4–20 mA, ±20 mA). The output circuits are isolated between channels and from the backplane bus at 75 V DC / 60 V AC, with a type test of 707 V DC. Diagnostics include wire-break and short-circuit detection, a group error LED, and a green/red DIAG LED for module status. Channel status is indicated per output by a green LED.

Physical Integration and Wiring

Voltage outputs require a minimum load of 2 kΩ; current outputs drive up to 500 Ω. Shielded cable recommended, up to 1 000 m for current signals and 200 m for voltage outputs. Isolation tested at 707 V DC between circuits. The module draws a maximum of 150 mA from the backplane, typical power loss 1.5 W. That's modest for a 4-channel analog output — leaves headroom in your 24 V DC supply budget.

Frequently asked questions

What is the depth of this module?

The depth is 58 mm, as listed in the specifications.

What does MSO 'No' mean?

MSO stands for Manufacturer's Service Obligation; 'No' means there is no mandatory support contract tied to this part. It is a standard catalog item.

MPN
6AG1135-6HD00-7BA1