Skip to main content
Siemens 6AG1135-6TD00-2CA1 — PLCs (Programmable Logic Controllers)

6AG1135-6TD00-2CA1 Analog Output, 4 Ch, 16-bit, HART

MPN6AG1135-6TD00-2CA1
Active

Siemens SIPLUS S7-1200 6AG1135-6TD00-2CA1, 4 analog outputs, 16-bit signed, HART, 0-20 mA / 4-20 mA, diagnostics, 24 V DC, 1.7 W, 58 x 15 x 73 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1135-6TD00-2CA1 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)115 mA
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)1.7 W
6AG1135-6TD00-2CA1 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)60 °C; = Tmax; +70 °C with configured empty slots to the left and right of the module
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1135-6TD00-2CA1 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)31 g

Product details

What it is & what it does

The Siemens 6AG1135-6TD00-2CA1 is an analog output module for the SIPLUS S7-1200 system, designed for extended temperature range applications. It provides four analog outputs, each configurable for 0 to 20 mA or 4 to 20 mA with 16-bit signed resolution. HART protocol is supported per channel, allowing simultaneous analog control and HART communication on the same loop. Each output channel includes wire-break and short-circuit detection, diagnostic alarms, and green/red LED indication. The module reports diagnostic data via I&M data (I&M0 to I&M3) and supports firmware updates. Power draw is 1.7 W typical at 24 V DC, with a maximum current consumption of 125 mA. Module-wide supply voltage monitoring is included.

The module mounts on a DIN rail using Siemens BaseUnits type A0 or A1, occupying a single 15 mm wide slot. Depth is 58 mm, height 73 mm. Isolation tested at 707 V DC between circuits. Galvanic isolation between the module and backplane: 60 V DC / 30 V AC between different circuits. Operating temperature: horizontal installation allows 0 to 60 °C (up to 70 °C with configured empty slots left and right), vertical installation 0 to 50 °C. Minimum -40 °C including condensation and frost.

Frequently asked questions

Will this module fit in a panel designed for 6AG1123-2DB03-2AX0?

Physically, the outer dimensions match the S7-1200 form factor (same width, depth, height). However, 6AG1123-2DB03-2AX0 is a digital input module. The analog output module uses different BaseUnit types (A0/A1) and has different wiring. Backplane compatibility is the same, but rewiring the field termination is required.

MPN
6AG1135-6TD00-2CA1