Siemens SIMATIC ET 200SP PROFINET interface module, 6AG1155-6AU00-7HM0, 2 ports via BusAdapter, MRP client, 2.4 W, I2t 0.36 A²·s.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1155-6AU00-7HM0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)2.4 W
Short-circuit protectionYes
6AG1155-6AU00-7HM0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)70 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1155-6AU00-7HM0 — Mechanical
ParameterValue
Width50 mm
Height138 mm
Depth89 mm
Weight (approx.)192 g; without BusAdapter

Product details

PROFINET Interface for ET 200SP – Active, No IRT

The Siemens 6AG1155-6AU00-7HM0 is a PROFINET IO Device interface module for the ET 200SP distributed I/O system. It mounts on the left side of the station and provides two network ports via a compatible BusAdapter — choose BA 2x RJ45, BA 2x M12, BA 2x FC, or fiber options. It supports MRP as a client for media redundancy but does not support IRT or MRPD, so it is suited for standard real-time networks, not isochronous motion applications. The integrated switch handles 100 Mbit/s full duplex with autonegotiation and autocrossing.

Frequently asked questions

What is the listed I2t rating and what does it mean?

The module's I2t rating is 0.36 A²·s, typically representing the thermal energy it can withstand from a surge or inrush event. For a communication interface, this indicates robust protection against transient currents.

Does this module support IRT or MRPD?

No, it does not support IRT (isochronous real-time) or MRPD (media redundancy with planned duplication). It supports MRP as a client for media redundancy, which is sufficient for standard ring topologies but not for high-speed deterministic motion control.

What BusAdapters are compatible?

The module accepts any of the listed BusAdapters: BA 2x RJ45, BA 2x M12, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC, BA 2x LC-LD, BA LC-LD / RJ45, BA LC-LD / M12.

MPN
6AG1155-6AU00-7HM0