Skip to main content
Siemens 6AG1155-6AU01-7CN0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1155-6AU01-7CN0 PROFINET BusAdapter, IRT

MPN6AG1155-6AU01-7CN0
NRND

Siemens 6AG1155-6AU01-7CN0 PROFINET BusAdapter, 2 ports, IRT high performance, 0.25 A²·s, 24 V DC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

6AG1155-6AU01-7CN0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)2.4 W
6AG1155-6AU01-7CN0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)70 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1155-6AU01-7CN0 — Mechanical
ParameterValue
Width50 mm
Height117 mm
Depth74 mm
Weight (approx.)120 g; without BusAdapter

Product details

The Siemens 6AG1155-6AU01-7CN0 PROFINET BusAdapter brings two ports to the ET 200AL family, carrying IRT with high performance down to 250 µs cycles — jitter holds under 1 µs, so it fits into motion-control isochronous loops without additional latency. The module draws 2.4 W from the 24 V DC rail, with a 50 mm footprint that slides onto the DIN rail alongside other ET 200AL slices.

Key ratings so-what

I2t is listed at 0.25 A²·s — that's the internal fuse energy rating, so upstream protection should coordinate below that threshold to avoid nuisance trips. IRT with high performance supports cycle times from 250 µs to 4 ms in 125 µs frames, plus standard IRT at 250 µs, 500 µs, 1 ms, 2 ms, and 4 ms. That gives flexibility for both high-speed and standard isochronous applications. Supports MRP, LLDP, SNMP, I&M0–I&M3, and Shared Device — so it integrates into managed PROFINET networks with redundancy and diagnostics.

MPN
6AG1155-6AU01-7CN0