PROFIBUS DP slave for extended conditions
The 6AG1155-6BA00-7CN0: It draws up to 250 mA from 24 VDC (19.2 to 28.8 V permissible), with a typical power loss of 1.5 W. Reverse polarity protection and a 5 ms ride-through on supply failure are built in. The module includes diagnostic functions, alarm generation (process and diagnostic), FREEZE and SYNC capabilities, and I&M data (I&M0 to I&M3) for asset tracking. Status indicators: RUN (green), ERROR (red), MAINT (yellow), and a green DP connection LED. PWR-LED monitors supply voltage. Rated isolation between supply and all other circuits is 707 V DC type test, with base isolation of 75 V DC / 60 V AC between different circuits.
Lifecycle and sourcing status
The extended temperature rating (-40 to 70 °C horizontal, -40 to 50 °C vertical with startup at -25 °C) means it is suited for unheated cabinets or outdoor cabinets in demanding environments.