6AG1193-4CF50-7AA0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Temperature, min.-40 °C; = Tmin
Temperature, max.70 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1193-4CF50-7AA0 — Mechanical
ParameterValue
Width30 mm
Height157 mm
Depth43 mm
Weight (approx.)131 g
6AG1193-4CF50-7AA0 — Other specifications
ParameterValue
CE markYes
Delivery quantity in pieces1
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)

Product details

What the extended temperature range buys you

The 6AG1193-4CF50-7AA0: The conformal coating protects against condensation that forms when a cold cabinet warms up; the standard 6ES7193-4CF50-0AA0 lacks that coating.

Harsh environment qualification — what it actually means

Certified to ANSI/ISA-71.04 class GX for corrosive gas exposure (excluding trichlorethylene), plus level LC3 salt spray and LB3 oil resistance. That means it survives in chemical processing zones, offshore platforms, and machine-tool coolant mist — environments where a standard terminal module would see contact corrosion within months. Altitude derating is specified: full temperature range at 1 140 to 795 hPa (-1 000 to +2 000 m), then a 10 K reduction up to 3 500 m, and a 20 K reduction up to 5 000 m. If your panel sits at 3 000 m, budget for a 70 °C ceiling dropping to 60 °C.

Physical fit — panel integration

30 mm wide, 157 mm tall, 43 mm deep — snaps onto the standard ET 200S DIN-rail mounting rail. The spring-loaded terminals accept 4x6 connections with access to AUX1 and AUX1 continuous, which means you can daisy-chain the auxiliary bus without extra jumpers.

Frequently asked questions

What is the difference between 6AG1193-4CF50-7AA0 and 6ES7193-4CF50-0AA0?

The 6AG1193-4CF50-7AA0 is the SIPLUS version with conformal coating and an extended temperature range of -40 to +70 °C, based on the standard 6ES7193-4CF50-0AA0. The standard version lacks conformal coating and has a narrower temperature range.

Is 6AG1193-4CF50-7AA0 compatible with standard ET 200S modules?

Yes, it is a SIPLUS ET 200S TM-E30C46-A1 terminal module designed for the ET 200S system. It mounts on the same DIN rail and interfaces with standard ET 200S electronic modules.

MPN