The 6AG1195-7HA00-2XA0: This SIPLUS ET 200M active bus module takes the place of the standard 6ES7195-7HA00-0XA0 and adds a conformal coating plus a wider temperature swing from -40 °C to 70 °C. It holds one power supply and one IM 153 interface module and supports hot swapping during Run — so you don't have to cycle the whole rack to swap a module. The bus cover is included. Conformal coating resists harmful gas concentrations, salt spray, and oil. Temperature range from -40 °C to 70 °C. Above 2 000 m, reduce max by 10 K to 3 500 m and by 20 K to 5 000 m.

6AG1195-7HA00-2XA0 SIPLUS ET 200M Active Bus Module, -40..70
MPN6AG1195-7HA00-2XA0
Siemens SIPLUS ET 200M Active Bus Module 6AG1195-7HA00-2XA0, -40 to +70°C, conformal coating, for PS and IM153.
$95.25Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Environmental
| Parameter | Value |
|---|---|
| Installation altitude, max. | 5 000 m |
| Temperature, min. | -40 °C |
| Temperature, max. | 70 °C |
| Ambient temperature vs. altitude/pressure derating | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Mechanical
| Parameter | Value |
|---|---|
| Width | 97 mm |
| Height | 92 mm |
| Depth | 30 mm |
| Weight (approx.) | 111 g |
Other specifications
| Parameter | Value |
|---|---|
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
Product details
Frequently asked questions
What is the maximum ambient temperature for this bus module?
Maximum ambient temperature is 70 °C, with altitude derating: above 2 000 m, reduce the max by 10 K up to 3 500 m and by 20 K up to 5 000 m.
What is the minimum ambient temperature?
Minimum ambient temperature is -40 °C, with cold start capability down to -25 °C.
Does the module have conformal coating and environmental resistance?
Yes, it includes conformal coating (Class A per IPC-CC-830A) and complies with ANSI/ISA-71.04 Level GX group A/B (excluding trichlorethylene), level LC3 salt spray, and level LB3 oil. It is also resistant to commercially available coolants and lubricants.