Skip to main content
Siemens 6AG1212-1BE40-2XB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1212-1BE40-2XB0 SIPLUS S7-1200, -40 to 70°C

MPN6AG1212-1BE40-2XB0
Active

Siemens SIPLUS S7-1200, 6AG1212-1BE40-2XB0, ruggedized CPU with -40 to 70 °C ambient, 20.4-28.8 V DC supply, PROFINET, MODBUS TCP, FBD/LAD/SCL programming.

$898.03Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1212-1BE40-2XB0 — I/O
ParameterValue
Digital inputs8; Integrated
Digital outputs6; Relays
6AG1212-1BE40-2XB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)0.085 µs; / Operation
Execution time, word operations (typ.)1.7 µs; / Operation
Execution time, floating-point arithmetic (typ.)2.3 µs; / Operation
Size, max.4 kbyte; Size of bit memory address area
6AG1212-1BE40-2XB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6AG1212-1BE40-2XB0 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)80 mA at 120 V AC; 40 mA at 240 V AC
Power loss (typ.)11 W
6AG1212-1BE40-2XB0 — Environmental
ParameterValue
Installation altitude, max.2 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 132 V AC
6AG1212-1BE40-2XB0 — Mechanical
ParameterValue
Width90 mm
Height100 mm
Depth75 mm
Weight (approx.)425 g
6AG1212-1BE40-2XB0 — Communication
ParameterValue
Interface typePROFINET

Product details

The Siemens 6AG1212-1BE40-2XB0 is a SIPLUS S7-1200 CPU – the wide-temperature, wide-supply variant of the standard 6ES7212-1BE40-0XB0. Rated -40 to 70 °C and 20.4-28.8 V DC, it runs in environments where a standard CPU can't: unheated cabinets, outdoor enclosures, dairy lines, refrigerated warehouses. Programming in FBD, LAD, and SCL, with an integrated 1 Mbyte code memory. PID controller, web server, and forcing are built in.

Same 100×90×75 mm footprint, same PROFINET interface (with shared device support). The SIPLUS adds the extended temperature range and the wider supply tolerance – otherwise pinout and function are identical.

Integration notes

PROFINET on the built-in port – no module needed. For PROFIBUS or AS-Interface, add the CM 1243-5 or respective master module. MODBUS TCP and UDP are software-selectable on the same port. Supply range 20.4-28.8 V DC; typical backup time is 480 h for the real-time clock. Watch the current draw on the backplane if populating all signal boards.

Frequently asked questions

Does this PLC support FBD and LAD programming?

Yes. The 6AG1212-1BE40-2XB0 supports FBD (function block diagram), LAD (ladder logic), and SCL (structured text) as part of the TIA Portal engineering.

Will it drop into a panel designed for 6ES7212-1BE40-0XB0 without rewiring?

Yes. The SIPLUS shares the same 100×90×75 mm dimensions, same pinout, and same PROFINET port. No rewiring needed – just swap the unit.

MPN
6AG1212-1BE40-2XB0