Skip to main content
Siemens 6AG1214-1AE30-5XB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1214-1AE30-5XB0 S7-1200 CPU, 2 MB, -40 to 70 °C

MPN6AG1214-1AE30-5XB0

Siemens S7-1200 CPU, 6AG1214-1AE30-5XB0, 2 MB work memory, 1,024 byte I/O image, FBD/LAD/SCL, PROFINET, -40 to 70 °C, cULus/CE.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

6AG1214-1AE30-5XB0 — I/O
ParameterValue
Digital inputs14; Integrated
Digital outputs10
ExpandableNo
Input data area1 024 byte
Output data area1 024 byte
6AG1214-1AE30-5XB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)0.1 µs; / Operation
Execution time, word operations (typ.)12 µs; / Operation
Execution time, floating-point arithmetic (typ.)18 µs; / Operation
6AG1214-1AE30-5XB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6AG1214-1AE30-5XB0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)12 W
Short-circuit protectionNo; to be provided externally
6AG1214-1AE30-5XB0 — Environmental
ParameterValue
Temperature, min.-40 °C
Temperature, max.70 °C
Operating temperature, min. (horizontal mounting)-25 °C; = Tmin
Operating temperature, max. (horizontal mounting)55 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1214-1AE30-5XB0 — Mechanical
ParameterValue
Width110 mm
Height100 mm
Depth75 mm
Weight (approx.)415 g

Product details

CPU memory and I/O capacity

The 6AG1214-1AE30-5XB0: The 2 MB integrated work memory sets the program size ceiling — sufficient for medium-complexity machine sequences with HMI and fieldbus overhead. The entire project is held in the integral EEPROM without battery backup, so the maintenance-free retention eliminates the common failure mode of a discharged capacitor bank on power loss. The I/O image supports 1,024 bytes each for inputs and outputs. This bounds the distributed I/O count without a separate expansion rack — plan the signal count against this ceiling before committing the BOM.

Environmental range and supply tolerance

Rated for -40 to 70 °C ambient, this CPU fits unheated outdoor cabinets or freezer-zone enclosures where standard S7-1200s would drift out of spec. The 24 V DC supply accepts 20.4 to 28.8 V — a 15 % tolerance band that rides through brownout dips on shared control transformers without dropping into undervoltage reset. The 240-hour typical backup time for the real-time clock and retentive data means the CPU holds its state through a long weekend power outage without external UPS support.

Programming languages and fieldbus

Supports FBD, LAD, and SCL — covers both ladder-logic legacy code reuse and structured-text math blocks for motion or process sequences. The SCL compiler lets you write PID loop tuning routines directly in the CPU without a separate function block library. PROFINET IO controller with TCP/IP support integrates into Siemens-centric architectures. No PROFIBUS or MODBUS on this variant — if the existing field devices speak RS-485 or MODBUS RTU, a communication processor or gateway is required.

Compliance and approvals

Carries cULus, CE, and UL approvals — covers North American and European panel certification without additional agency review. No FM approval on this variant.

Frequently asked questions

What programming languages does the 6AG1214-1AE30-5XB0 support?

FBD, LAD, and SCL are all supported. This covers ladder logic for legacy machine programs and structured text for complex math or PID loops.

Can the 6AG1214-1AE30-5XB0 replace a standard S7-1200 in an existing panel?

The form factor and PROFINET interface match the standard S7-1200 family, so a drop-in replacement is mechanically possible. The key difference is the wider -40 to 70 °C temperature range — confirm the existing enclosure's thermal profile before swapping. The I/O image and memory are identical to the standard 2 MB variant.

MPN
6AG1214-1AE30-5XB0