Skip to main content
Siemens 6AG1214-1BG40-4XB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1214-1BG40-4XB0 SIPLUS S7-1200 CPU, -40 to 70°C

MPN6AG1214-1BG40-4XB0
Active

Siemens SIPLUS S7-1200 CPU 1214C, 6AG1214-1BG40-4XB0, extended -40 to 70°C, PROFINET, MODBUS TCP, 4 Mbyte load memory, backup 480 h.

$1,069.08Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1214-1BG40-4XB0 — I/O
ParameterValue
Digital inputs14; Integrated
Digital outputs10; Relays
6AG1214-1BG40-4XB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)0.085 µs; / instruction
Execution time, word operations (typ.)1.7 µs; / instruction
Execution time, floating-point arithmetic (typ.)2.3 µs; / instruction
Size, max.8 kbyte; Size of bit memory address area
6AG1214-1BG40-4XB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6AG1214-1BG40-4XB0 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)100 mA at 120 V AC; 50 mA at 240 V AC
Power loss (typ.)14 W
6AG1214-1BG40-4XB0 — Environmental
ParameterValue
Installation altitude, max.2 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 132 V AC
6AG1214-1BG40-4XB0 — Mechanical
ParameterValue
Width110 mm
Height100 mm
Depth75 mm
Weight (approx.)455 g
6AG1214-1BG40-4XB0 — Communication
ParameterValue
Interface typePROFINET

Product details

Integrator's field note

The 6AG1214-1BG40-4XB0: This is the SIPLUS AC/DC/RLY CPU 1214C — the extended-temperature, conformal-coated variant of the standard S7-1200. The operating range spans -40 to 70°C, so it suits unheated enclosures or installations with thermal cycling. PROFINET with shared-device capability is onboard; MODBUS TCP and UDP are handled natively. For PROFIBUS, add a CM 1243-5 module. The 4 Mbyte load memory holds code and tags without a separate memory card. Backup retains the project for 480 h typical.

What makes this different from the standard CPU

The SIPLUS variant provides -40 to 70°C and conformal coating. Footprint is 110×100×75 mm.

Frequently asked questions

Does 6AG1214-1BG40-4XB0 support FBD, LAD, and SCL programming?

Yes. The CPU supports FBD, LAD, and SCL programming languages, so it integrates with existing Siemens TIA Portal projects using any of those methods.

What is the operating temperature range for this SIPLUS CPU?

It operates from -40°C to 70°C, making it suitable for unheated or extreme environment installations.

What communication protocols are supported without additional modules?

Onboard protocols include PROFINET (shared device), MODBUS TCP (client and server), UDP, and TCP/IP. For PROFIBUS you need the CM 1243-5 module.

How much load memory does this CPU have?

It has 4 Mbyte of integrated load memory for program code and data. A separate memory card is not required for typical applications.

MPN