Skip to main content
Siemens 6AG1214-1HG31-5XB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1214-1HG31-5XB0 S7-1200 CPU, 24V, -40…70°C

MPN6AG1214-1HG31-5XB0

Siemens S7-1200 CPU 1214C, 6AG1214-1HG31-5XB0, DC/DC/DC, 24 V supply, -40…70 °C, 1024 byte I/O, 4 MB memory, PROFINET, Modbus TCP, LAD/FBD/SCL.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1214-1HG31-5XB0 — I/O
ParameterValue
Digital inputs14; Integrated
Digital outputs10; Relays
ExpandableNo
Input data area1 024 byte
Output data area1 024 byte
6AG1214-1HG31-5XB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)0.085 µs; / instruction
Execution time, word operations (typ.)1.7 µs; / instruction
Execution time, floating-point arithmetic (typ.)2.5 µs; / instruction
Size, max.8 kbyte; Size of bit memory address area
6AG1214-1HG31-5XB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6AG1214-1HG31-5XB0 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)500 mA; Typical
Permissible range, lower limit (DC)5 V
Permissible range, upper limit (DC)250 V
Power loss (typ.)12 W
Short-circuit protectionNo; to be provided externally
6AG1214-1HG31-5XB0 — Environmental
ParameterValue
Installation altitude, max.2 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
Operating temperature, max. (horizontal mounting)60 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 132 V AC
6AG1214-1HG31-5XB0 — Mechanical
ParameterValue
Width110 mm
Height100 mm
Depth75 mm
Weight (approx.)435 g
6AG1214-1HG31-5XB0 — Communication
ParameterValue
Interface typePROFINET

Product details

CPU core and programming

The 6AG1214-1HG31-5XB0: Operating temperature spans -40 °C to 70 °C, covering cold storage and hot panel environments. Integrated 4 Mbyte memory holds user program and data; backup time is 480 h typical for retentive data.

Connectivity and I/O

Built-in PROFINET interface handles real-time automation comms. Also on board: PROFIBUS, Modbus TCP/IP, AS-Interface. Supports UDP, forcing, and autocrossing. Digital I/O address area: 1 024 byte inputs, 1 024 byte outputs. Analog input: 0 to +10 V, adjustable. Two-wire sensor thresholds: signal 0 at 5 V DC at 1 mA; signal 1 at 15 V DC at 2.5 mA.

Multi-protocol and control features

Functions as Modbus TCP client and server. PROFIsafe is not supported, so separate safety controller is required. PID controller integrated for closed-loop applications. Isolated voltage supply on the sensor side. Forcing and present monitoring are available as standard.

Physical dimensions

Compact footprint: 110 mm wide, 100 mm high, 75 mm deep — fits within standard S7-1200 cutout. No expansion slots available (non-expandable per the spec).

Frequently asked questions

What programming languages does the 6AG1214-1HG31-5XB0 support?

It supports LAD (ladder logic), FBD (function block diagram), and SCL (structured text).

What is the supply voltage and temperature range?

The DC supply range is 20.4 V to 28.8 V. Operating temperature is -40 °C to 70 °C.

What fieldbus interfaces are available?

PROFINET, PROFIBUS, Modbus TCP/IP, AS-Interface, and UDP are supported.

How much memory and backup time does it have?

Integrated 4 Mbyte memory for program and data. Backup time is 480 h typical for retentive variables.

MPN
6AG1214-1HG31-5XB0