Skip to main content
Siemens 6AG1215-1HG31-2XB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1215-1HG31-2XB0 SIPLUS S7-1200, -40 to 70°C

MPN6AG1215-1HG31-2XB0

Siemens SIPLUS S7-1200 CPU, 6AG1215-1HG31-2XB0, 24 V DC, -40…70 °C, PROFINET, PROFIBUS, 4 Mbyte memory.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1215-1HG31-2XB0 — I/O
ParameterValue
Digital inputs14; Integrated
Digital outputs10; Relays
Input data area1 024 byte
Output data area1 024 byte
6AG1215-1HG31-2XB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)0.085 µs; / instruction
Execution time, word operations (typ.)1.7 µs; / instruction
Execution time, floating-point arithmetic (typ.)2.5 µs; / instruction
Size, max.8 kbyte; Size of bit memory address area
6AG1215-1HG31-2XB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6AG1215-1HG31-2XB0 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)500 mA; Typical
Permissible range, lower limit (DC)5 V
Permissible range, upper limit (DC)250 V
Power loss (typ.)12 W
Short-circuit protectionNo; to be provided externally
6AG1215-1HG31-2XB0 — Environmental
ParameterValue
Installation altitude, max.2 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
Operating temperature, max. (horizontal mounting)70 °C; = Tmax; > +60 °C Number of simultaneously controllable inputs and outputs max. 50 %; no signal board can be used
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 132 V AC
6AG1215-1HG31-2XB0 — Mechanical
ParameterValue
Width130 mm
Height100 mm
Depth75 mm
Weight (approx.)585 g
6AG1215-1HG31-2XB0 — Communication
ParameterValue
Interface typePROFINET

Product details

Field-ready PLC for extreme conditions

This 6AG1215-1HG31-2XB0 is a SIPLUS S7-1200 CPU designed to live where a standard S7-1200 won't — rated for -40 to 70 °C ambient, so it can ride a chiller roof or a desert solar tracker without derating. Runs on 24 V DC, offers PROFINET and PROFIBUS onboard, and supports LAD, FBD, and SCL out of the box. That means you can program it in whatever dialect your line uses, no translation needed.

Clutch specs for a line-down swap

Backup time 480 h typical holds program through swap. Forcing, MODBUS TCP, UDP, AS-Interface, and 1 024 byte I/O image are onboard.

Measures 130 x 100 x 75 mm — standard S7-1200 footprint, so it bolts into existing DIN rail assemblies without drilling. The 24 V DC supply is isolated, and it handles 2-wire sensors on the inputs with a signal threshold of 15 V DC at 2.5 mA for a "1" and 5 V DC at 1 mA for a "0". Autocrossing and autonegotiation are baked into the PROFINET port, so no manual IP trickery on a swap. Just wire the 24 V, connect the network, and let it link up.

Frequently asked questions

What temperature range can this CPU handle?

-40 to 70 °C ambient, making it suitable for outdoor or extreme indoor environments.

What programming languages does it support?

LAD (ladder logic), FBD (function block diagram), and SCL (structured text) are all supported.

What communication interfaces are built in?

PROFINET (with autocrossing and autonegotiation), PROFIBUS, MODBUS TCP, UDP, and AS-Interface.

MPN
6AG1215-1HG31-2XB0