Specifications

6AG1222-1BF30-2XB0 — Outputs
ParameterValue
Digital outputs8
6AG1222-1BF30-2XB0 — Electrical
ParameterValue
Rated value (DC)24 V
Output current, resistive load, max.0.5 A
Output current at signal "1" (rated)0.5 A
Permissible range, upper limit (DC)28.8 V
Permissible range, lower limit (DC)20.4 V
Output voltage at signal "1" (min.)20 V DC
Residual current at signal "0", max.10 µA
Current consumption from backplane bus (5 V DC), max.120 mA
Power dissipation (typ.)1.5 W
Inductive shutdown voltage clamptyp. (L+) -48 V
Isolation between channels and backplane bus500 V AC
Isolation, channels in groups of1
6AG1222-1BF30-2XB0 — Protection & Diagnostics
ParameterValue
Short-circuit protectionNo; to be provided externally
Diagnostics functionYes
Diagnostic alarmYes
6AG1222-1BF30-2XB0 — Performance
ParameterValue
Output switching delay 0 to 1, max.50 µs
Output switching delay 1 to 0, max.200 µs
Switching frequency, inductive load, max.0.5 A
Switching frequency, lamp load, max.5 W
6AG1222-1BF30-2XB0 — Mechanical & Connection
ParameterValue
Cable length, unshielded, max.150 m
Cable length, shielded, max.500 m
Width45 mm
Height100 mm
Depth75 mm
Weight (approx.)180 g

Product details

8 outputs at 0.5 A — a straightforward S7-1200 slice

The 6AG1222-1BF30-2XB0 gives you eight digital outputs rated 0.5 A each on resistive or inductive loads. Nominal 24 V DC, permitted range 20.4 to 28.8 V. That's the standard S7-1200 output spec — good for driving contactors, solenoid valves, or indicator lamps in a compact control panel. Output switching is crisp: 50 µs on, 200 µs off. Diagnostics on the bus flag short-circuit or wire-break — no need to trace each loop separately.

Not a drop-in for the 32-output sibling

This 8-output module draws 120 mA max from the 5 V DC backplane bus. The 1BH32 variant requires a different backplane budget and field wiring — verify compatibility before substitution.

Panel mounting and wiring notes

Dimensions: 100 mm × 45 mm × 75 mm — takes up three width units in the S7-1200 rack. Short-circuit protection must be provided externally per the spec. Use a 0.5 A fuse or electronic breaker per output group (outputs are isolated in groups of 1). The module limits inductive shutdown voltage to typ. (L+) -48 V, which helps protect downstream drivers. Cable length: shielded up to 500 m, unshielded up to 150 m. For a noisy bottling line, go shielded.

Frequently asked questions

What is the temperature range for this module?

Rated for -40 °C to 70 °C ambient.

Does the 6AG1222-1BF30-2XB0 have CE and FM approval?

Yes, it carries both CE marking and FM approval.

Is short-circuit protection built in?

No, short-circuit protection must be provided externally per the specification.

MPN