Skip to main content
Siemens 6AG1222-1XF32-2XB0 — Digital Output Modules

Siemens 6AG1222-1XF32-2XB0 SIPLUS 8-Relay Output, -40 to 70°

MPN6AG1222-1XF32-2XB0
Active

Siemens SIPLUS 6AG1222-1XF32-2XB0, current-production relay output module, 8 channels, 2 A per channel, -40 to 70 °C, marine approved.

$580.62Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1222-1XF32-2XB0 — Outputs
ParameterValue
Digital outputs8
6AG1222-1XF32-2XB0 — Electrical
ParameterValue
Rated value (DC)5 V DC to 30 V DC
Output current, resistive load, max.2 A
Output current, max. per circuit / per module2 A
Permissible range, upper limit (DC)28.8 V
Permissible range, lower limit (DC)20.4 V
Current consumption from backplane bus (5 V DC), max.140 mA
Power dissipation (typ.)5 W
Isolation between channelsRelays
Isolation between channels and backplane bus1 500 V AC for 1 minute
Isolation, channels in groups of1
6AG1222-1XF32-2XB0 — Protection & Diagnostics
ParameterValue
Short-circuit protectionNo; to be provided externally
Diagnostics functionYes
Diagnostic alarmYes
6AG1222-1XF32-2XB0 — Performance
ParameterValue
Output switching delay 0 to 1, max.10 ms
Output switching delay 1 to 0, max.10 ms
Switching frequency, inductive load, max.2 A
Switching frequency, lamp load, max.30 W with DC, 200 W with AC
6AG1222-1XF32-2XB0 — Mechanical & Connection
ParameterValue
Cable length, unshielded, max.150 m
Cable length, shielded, max.500 m
Width45 mm
Height100 mm
Depth75 mm
Weight (approx.)310 g

Product details

SIPLUS 8-Relay Output for Extreme Environments

The Siemens 6AG1222-1XF32-2XB0 is an active-production SIPLUS digital output module delivering eight relay outputs rated at 2 A per channel for both resistive and inductive loads. Its -40 to 70 °C operating temperature range allows it to be mounted in unheated enclosures, cold warehouses, or hot machine cabinets without derating. The module switches AC loads from 5 to 250 V and DC loads from 5 to 30 V, covering the common coil and indicator voltages found in most industrial cabinets. Marine approval and IP20 protection make the module suitable for shipboard and coastal installations, provided it is mounted inside a suitable enclosure. Front-side diagnostics give per-channel status and alarm reporting, which speeds up fault finding when a field device stops responding.

Installation & Wiring Notes

The module occupies 45 mm of DIN-rail width and requires a front connector — order separately. External short-circuit protection must be provided. The relay coil draws 16.7 mA from the load voltage L+, and the backplane bus supplies 140 mA at 5 V DC. Overall power loss is typically 5 W. Isolation between channels is by relay, with 750 V AC for 1 minute between different circuits and 1 500 V AC between channels and the backplane bus. Unshielded cables can run up to 150 m, shielded up to 500 m.

Field Diagnostics & Mechanical Endurance

Each output channel provides status indication and the module can generate diagnostic alarms. Transition times from 0 to 1 and 1 to 0 are both capped at 10 ms, adequate for most discrete control signals. The relays are rated for 10 million mechanical cycles, but at rated load voltage the contact endurance drops to 100 000 cycles — factor that into life planning for frequently switched applications. Cold restart is tested down to -25 °C.

Frequently asked questions

What is the operating temperature range of this module?

It is rated for -40 to 70 °C, with a cold restart minimum of -25 °C.

MPN
6AG1222-1XF32-2XB0