Integration & wiring
The 6AG1223-1BH32-2XB0: Mounts on a standard DIN rail (IP20) and requires a front connector. Shielded cable runs up to 500 m, unshielded up to 150 m. Input thresholds: signal '0' at 5 V DC / 1 mA, signal '1' at 15 V DC / 2.5 mA. Diagnostic alarm and status readback are built in – useful when the panel is miles down the route.