Skip to main content
Siemens 6AG1223-1BL30-2XB0 — PLC I/O & Expansion Modules

Siemens 6AG1223-1BL30-2XB0 S7-1200 DI/DO, 16/16, 24VDC

MPN6AG1223-1BL30-2XB0

Siemens SIMATIC S7-1200, digital I/O module, 6AG1223-1BL30-2XB0, 16 DI / 16 DO, 24 VDC, -40 to 70 °C, diagnostics, alarms.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

6AG1223-1BL30-2XB0 — I/O
ParameterValue
Digital inputs16
Digital outputs16
6AG1223-1BL30-2XB0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
For signal "1"15 V DC at 2.5 mA
For signal "0"5 V DC at 1 mA
Current for signal "1" (typ.)4 mA
Max.70 °C
Power loss (typ.)4.5 W
Current consumption from backplane bus (5 V DC), max.185 mA
Current consumption from load voltage L+ (no load), max.4 mA; per channel
Short-circuit protectionNo; to be provided externally
Isolation: channels to backplane bus500 V AC
Max. cable length, shielded500 m
Max. cable length, unshielded150 m
6AG1223-1BL30-2XB0 — Performance
ParameterValue
ParameterizableYes
Diagnostic alarmYes
Diagnostics functionYes
6AG1223-1BL30-2XB0 — Environmental
ParameterValue
IP protection ratingIP20
Min.-40 °C
6AG1223-1BL30-2XB0 — Mechanical
ParameterValue
Height100 mm
Width70 mm
Depth75 mm
Weight (approx.)310 g
6AG1223-1BL30-2XB0 — Approvals
ParameterValue
CE markYes

Product details

Module overview

Siemens S7-1200 digital I/O module 6AG1223-1BL30-2XB0 packs 16 inputs and 16 outputs on 24 VDC, rated from -40 °C to 70 °C. On-board diagnostics and alarm functions reduce fault-finding time on the line. Carries cULus, CE, and FM approvals for plant-floor installation globally.

Lifecycle status is current — no phase-out or last-time-buy to chase.

Integration notes

Input thresholds: signal '1' at ≥20 VDC, 4 mA typical; signal '0' at ≤0.1 VDC with 10 kΩ load. Switching delays: 0→1 in 50 µs max, 1→0 in 200 µs max. Unshielded cable run up to 150 m; shielded up to 500 m. Typical power loss 4.5 W from the backplane. No short-circuit protection onboard — fuse externally.

Frequently asked questions

What temperature range does this module support?

Rated from -40 °C to 70 °C operating ambient.

What certifications does it carry?

cULus, CE mark, and FM approval.

MPN
6AG1223-1BL30-2XB0