Skip to main content
Siemens 6AG1231-5PD30-2XB0 — Analog Input Modules

Siemens 6AG1231-5PD30-2XB0 SIPLUS RTD Module, -40 to 70°C

MPN6AG1231-5PD30-2XB0

Siemens SIPLUS S7-1200, 6AG1231-5PD30-2XB0, 4-channel analog input for resistance thermometers, -40 to 70°C, Pt100/Ni100/Cu10, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

6AG1231-5PD30-2XB0 — Inputs & Signal Ranges
ParameterValue
Number of analog inputs4; Resistance thermometer
Resistance measuring rangesYes; 150 Ω, 300 Ω, 600 Ω
RTD support (resistance thermometer)Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000
Input range: 0 to 600 OhmYes
RTD type: Pt100Yes
RTD type: Pt200Yes
Permissible input voltage, max. (destruction limit)±35 V
6AG1231-5PD30-2XB0 — Measurement Performance
ParameterValue
Resolution (bit incl. sign), max.15 bit; + sign
Measurement principleintegrating
Temperature measurement error (±)25 °C ±0.1%, -25 °C to 70 °C ±0.4 % entire measuring range
Interference voltage suppression (at interference frequency)85 dB at 50 / 60 / 400 Hz
Common-mode interference suppression, min.120 dB
6AG1231-5PD30-2XB0 — Diagnostics & Monitoring
ParameterValue
Wire-break detectionYes
Diagnostic alarmYes
Diagnostics functionYes; Can be read out
Supply voltage monitoringYes
6AG1231-5PD30-2XB0 — Power
ParameterValue
Rated value (DC)24 V
Power loss, typ.1.5 W
6AG1231-5PD30-2XB0 — Mechanical
ParameterValue
Required front connectorYes
Width45 mm
Height100 mm
Depth75 mm
Weight, approx.220 g

Product details

The 6AG1231-5PD30-2XB0: 4-channel analog input module for resistance thermometers (RTDs), part of the Siemens SIPLUS S7-1200 family. Supports Pt100, Pt1000, Ni100, Ni1000, Cu10, and other common RTD types. Power loss is 1.5 W typical. The module requires a front connector (not included).

Integration

Width 45 mm, height 100 mm, depth 75 mm — fits a single S7-1200 slot. IP20 rated; suitable for clean, dry control cabinets. The integrating measurement principle means the input filters out high-frequency noise, but settling time per channel needs to be accounted for in scan-cycle planning. Diagnostics function can be read out via the backplane. Diagnostic alarm and input status bits are available — useful for wire-break detection on long RTD runs.

Frequently asked questions

What are the key temperature ratings?

The module is rated for operating temperatures from -40 °C to 70 °C.

What RTD probes does it support?

It supports Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, and LG-Ni1000 resistance-type transmitters.

What compliance documentation is available?

The module carries CE marking. No other compliance details (RoHS, REACH, UL) are listed in the specification.

MPN
6AG1231-5PD30-2XB0