Skip to main content
Siemens 6AG1232-4HB30-4XB0 — Analog Output Modules

Siemens 6AG1232-4HB30-4XB0 SIPLUS S7-1200 SM 1232

MPN6AG1232-4HB30-4XB0

Siemens SIPLUS S7-1200 SM 1232 analog output module, 2 outputs, 14-bit voltage / 13-bit current, conformal coated, -40 to 70 °C, IP20, 24 VDC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

6AG1232-4HB30-4XB0 — Outputs
ParameterValue
Number of analog outputs2; Current or voltage
Output range: -10 V to +10 VYes
Output range: 0 to 20 mAYes
Load resistance, current outputs, max.600 Ω
Load resistance, voltage outputs, min.1 000 Ω
6AG1232-4HB30-4XB0 — Performance
ParameterValue
Resolution (incl. sign, with overrange), max.14 bit; Voltage: 14 bit; Current : 13 bit
Error, voltage output (rel. to output range)0.3 %
Error, current output (rel. to output range)0.3 %
Temperature error (rel. to output range)25 °C ±0.3%, to 55 °C ±0.6% total measurement range
6AG1232-4HB30-4XB0 — Power
ParameterValue
Rated value (DC)24 V
Power loss (typ.)1.5 W
6AG1232-4HB30-4XB0 — Diagnostics
ParameterValue
Supply voltage monitoringYes
Diagnostics functionYes
Diagnostic interrupt/alarmYes
Wire-break detection (current outputs)Yes
Short-circuit detection (voltage outputs)Yes
6AG1232-4HB30-4XB0 — Environmental
ParameterValue
Temperature, max.70 °C
Temperature, min.-40 °C
6AG1232-4HB30-4XB0 — Mechanical
ParameterValue
Front connector requiredYes
Width45 mm
Height100 mm
Depth75 mm

Product details

Lifecycle and sourcing — active, conformal-coated spare part

The 6AG1232-4HB30-4XB0: This is a current-production SIPLUS spare part based on the standard 6ES7232-4HB30-0XB0, with conformal coating that protects the board in humid or condensing environments.

Analog output specs — two channels, voltage or current

Two analog outputs, each configurable for voltage (±10 V) or current (0–20 mA). Voltage resolution is 14 bits; current resolution is 13 bits. With voltage outputs the minimum load is 1000 Ω; with current outputs the maximum load is 600 Ω. Accuracy is ±0.3 % of output range for both voltage and current, with temperature drift adding ±0.3 % at 25 °C and ±0.6 % total at 55 °C.

Power draw and backplane loading

Draws 45 mA typical from the 24 VDC field supply and 80 mA from the 5 VDC backplane bus. Total typical power loss is 1.5 W. The module requires a front connector (ordered separately) and fits a 45 mm wide slot in the S7-1200 rack.

Environmental range and approvals

Rated for -40 to 70 °C ambient, with altitude derating above 2000 m. IP20 enclosure — suitable for clean, dry cabinet environments. Carries CE and FM approvals; diagnostics include wire-break, short-circuit, and supply-voltage monitoring.

MPN