Skip to main content
Siemens 6AG1241-1CH32-4XB0 — PLC Communication Modules

Siemens 6AG1241-1CH32-4XB0 SIPLUS CM 1241 RS-422/485 Module

MPN6AG1241-1CH32-4XB0
Active

Siemens SIPLUS S7-1200 CM 1241 RS-422/485 communications module, conformal coated, -40…+70 °C, 30x100x75 mm, supports USS/ASCII library functions.

$564.03Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1241-1CH32-4XB0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, upper limit (DC)28.8 V
Permissible range, lower limit (DC)20.4 V
Power loss (typ.)1.2 W
6AG1241-1CH32-4XB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
6AG1241-1CH32-4XB0 — Mechanical
ParameterValue
Width30 mm
Height100 mm
Depth75 mm

Product details

The 6AG1241-1CH32-4XB0: This is the SIPLUS variant of the standard CM 1241 RS-422/485 module (6ES7241-1CH32-0XB0), conformal coated and rated for a wider temperature range of -40°C to +70°C. It handles USS and ASCII protocols as library functions in TIA Portal, and supports Freeport programming for custom serial links. The single RS-422/485 interface is on a 9-pin D-sub (male) – watch the pinout if you are replacing a standard unit, the connector orientation is the same. Power draw is typical 1.2 W from the 24 V DC backplane; the supply can sag to 20.4 V and still hold the module up.

Mechanical footprint is a slim 30 mm wide by 100 mm high by 75 mm deep – sits on standard DIN rail and leaves room for adjacent modules. Cable length to the remote device can run up to 1 000 m, but at that distance shield grounding matters: single-point on the D-sub shell at the module end keeps ground loops out of the RS-485 bus. The module is designed for altitudes up to 5 000 m with derating above 2 000 m; at sea level expect full 70°C ambient tolerance. Drop height rating is 0.3 m in the package – treat the conformal coating as environmental protection, not impact armor.

The lifecycle status is active – no last-time-buy or NRND flag. This part ships with the conformal coating already applied and the standard TIA Portal GSDML; no special firmware or library pack beyond what the base module uses.

Frequently asked questions

What protocols does the CM 1241 support?

USS and ASCII are available as TIA Portal library functions. Freeport programming is supported for custom serial protocols on the RS-422/485 interface.

What is the maximum ambient temperature for this module?

Rated for operation at 70 °C maximum, with the full temperature range covering -40 to +70 °C. Derating applies above 2 000 m altitude.

MPN
6AG1241-1CH32-4XB0