Siemens 6AG1305-1BA80-2AA0 SIPLUS S7-300 Power Supply

MPN6AG1305-1BA80-2AA0

Siemens SIPLUS S7-300 power supply, 6AG1305-1BA80-2AA0, 24V DC rated input, 2A output, 120x80x125 mm, EN 50155 railway certified.

$317.50Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1305-1BA80-2AA0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)23.27 V
Permissible range, upper limit (DC)24.72 V
Power loss (typ.)16 W
Short-circuit protectionYes; Electronic
6AG1305-1BA80-2AA0 — Environmental
ParameterValue
Installation altitude, max.2 000 m
Temperature, min.-25 °C; = Tmin
Temperature, max.70 °C; = Tmax; for use on railway vehicles according to EN 50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/UL hazardous use applies
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 75 V DC
6AG1305-1BA80-2AA0 — Mechanical
ParameterValue
Width80 mm
Height125 mm
Depth120 mm
Weight (approx.)740 g

Product details

Railway-rated 2A supply for S7-300 racks

The Siemens 6AG1305-1BA80-2AA0 is a SIPLUS S7-300 power supply that takes 24 V DC input and delivers a SELV 2 A output to the backplane bus.

Output current across the DC input range

The rated output current depends on the input voltage: 2.7 A at 24 V DC, 1.3 A at 48 V DC, 0.9 A at 72 V DC, 0.65 A at 96 V DC, and 0.6 A at 110 V DC. The supply accepts any DC voltage from 23.27 V up to the 110 V DC rated value, so it covers the full nominal range used in rolling stock and industrial battery-backed systems.

DIN rail footprint and thermal budget

Typical power loss is 16 W, and the supply is convection-cooled; the 70 °C max ambient rating means no derating in a sealed enclosure as long as the internal air stays below that ceiling. The 20 A inrush current lasts less than the 3 s power-up time, so the upstream breaker needs a C-curve or a slow-blow characteristic to avoid nuisance trips.

Frequently asked questions

Is 6AG1305-1BA80-2AA0 a direct replacement for 6ES7305-1BA80-0AA0?

Yes, the 6AG1305-1BA80-2AA0 is the SIPLUS version of the standard 6ES7305-1BA80-0AA0. It is pin-compatible and fits the same S7-300 rack slot. The difference is the extended temperature range and EN 50155 certification on the SIPLUS variant.

MPN
6AG1305-1BA80-2AA0