Skip to main content
Siemens 6AG1322-5FF00-4AB0 — Digital Output Modules

Siemens 6AG1322-5FF00-4AB0 8DO 2A -40 to 70°C

MPN6AG1322-5FF00-4AB0

Siemens S7-1500 digital output module, 8 DO, 2 A, 24 V DC, -40 to 70 °C, 40 mm, diagnostic alarms.

$468.63Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1322-5FF00-4AB0 — Outputs
ParameterValue
Digital outputs8
6AG1322-5FF00-4AB0 — Electrical
ParameterValue
Output current, resistive load, max.10 Hz
Output current at signal "1" (rated)2 A
Output voltage at signal "1" (min.)L1 (-8.5 V)
Residual current at signal "0", max.2 mA
Output current up to 60 °C, max.4 A
Current consumption from backplane bus (5 V DC), max.100 mA
Power dissipation (typ.)8.6 W
Isolation between channelsYes
Isolation between channels and backplane busYes; Optocoupler
Isolation, channels in groups of1
Isolation test voltage1 500 V AC
6AG1322-5FF00-4AB0 — Protection & Diagnostics
ParameterValue
Short-circuit protectionYes; to be provided externally; fuse 3.15 A / 250 V, quick response
Diagnostics functionYes; Parameterizable
Diagnostic alarmYes; Parameterizable
Redundant load controlYes
Output can drive a digital inputYes
6AG1322-5FF00-4AB0 — Performance
ParameterValue
Switching frequency, inductive load, max.0.5 Hz
Switching frequency, lamp load, max.1 Hz
6AG1322-5FF00-4AB0 — Mechanical & Connection
ParameterValue
Cable length, unshielded, max.600 m
Cable length, shielded, max.1 000 m
Width40 mm
Height125 mm
Depth120 mm
Weight (approx.)275 g

Product details

Siemens 6AG1322-5FF00-4AB0 digital output module, 8 channels, 2 A per channel with zero-crossing switching at 60 V. Diagnostic alarms; operating range -40 to 70 °C; 40 mm wide; requires 40-pin front connector.

Derating and protection

Resistive load switching is rated at 10 Hz, inductive at 0.5 Hz. Short-circuit protection is external — spec calls for a 3.15 A quick-blow fuse per channel group. Power dissipation is 8.6 W typical; keep adjacent modules spaced per manual thermal recommendations to stay at the rated 4 A through 60 °C.

Certifications

UL recognized under File E239877, CE, EAC, RCM, and KC approvals are listed on the module. Documentation for RoHS/REACH is available from Siemens upon request. The module carries a CE mark, meeting EU directives for industrial automation.

Frequently asked questions

What type of short-circuit protection does the module require?

Short-circuit protection must be provided externally. The spec recommends a 3.15 A / 250 V quick-response fuse per channel group.

Does 6AG1322-5FF00-4AB0 include diagnostics?

Yes, it has parameterizable diagnostic alarms and a group error SF (red) LED per channel.

MPN
6AG1322-5FF00-4AB0