Integrator note—4AI Ex i, 20 mA loops, 50 Ω burden
The 6AG1331-7RD00-2AB0: Four analog inputs accepting 0 to 20 mA or 4 to 20 mA, terminated on a 20-pin front connector. Input resistance sits at 50 Ω per channel, so the loop sees a standard burden. Module carries Ex i intrinsic safety protection—zone-mount with confidence. Reverse polarity protection on the 24 V DC supply. Diagnostics via red SF and per-channel F indicators; group error signal reports on the backplane.