Skip to main content
Siemens 6AG1331-7RD00-2AB0 — Analog Input Modules

Siemens 6AG1331-7RD00-2AB0 4AI Ex i, -40..70°C

MPN6AG1331-7RD00-2AB0

Siemens S7-300 4AI Ex i analog input module, 6AG1331-7RD00-2AB0, -40..70°C, ATEX II 3 G Ex nA, FM Class I Div2, 24V DC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

6AG1331-7RD00-2AB0 — Inputs & Signal Ranges
ParameterValue
Number of analog inputs4
Current input rangeYes
Voltage input rangeNo
Resistance measuring rangesNo
RTD support (resistance thermometer)No
Thermocouple support (types)No
Input range: 0 to 20 mAYes
Input range: 4 to 20 mAYes
Current measurement: 2-wire transducerYes
Current measurement: 4-wire transducerYes
Input resistance (0 to 20 mA)50 Ω
Input resistance (4 to 20 mA)50 Ω
Permissible input current, max. (destruction limit)40 mA
Max. shielded signal cable length200 m
6AG1331-7RD00-2AB0 — Measurement Performance
ParameterValue
Resolution (bit incl. sign), max.16 bit; 10 bit to 15 bit + sign
Current measurement error (±)0.1 %
Interference voltage suppression (at interference frequency)10 to 400 Hz
6AG1331-7RD00-2AB0 — Diagnostics & Monitoring
ParameterValue
Diagnostics functionYes
6AG1331-7RD00-2AB0 — Power
ParameterValue
Rated value (DC)24 V
Power loss, typ.3 W
Reverse polarity protectionYes
6AG1331-7RD00-2AB0 — Mechanical
ParameterValue
Required front connector20-pin
Width40 mm
Height125 mm
Depth120 mm
Weight, approx.290 g

Product details

Integrator note—4AI Ex i, 20 mA loops, 50 Ω burden

The 6AG1331-7RD00-2AB0: Four analog inputs accepting 0 to 20 mA or 4 to 20 mA, terminated on a 20-pin front connector. Input resistance sits at 50 Ω per channel, so the loop sees a standard burden. Module carries Ex i intrinsic safety protection—zone-mount with confidence. Reverse polarity protection on the 24 V DC supply. Diagnostics via red SF and per-channel F indicators; group error signal reports on the backplane.

Frequently asked questions

What temperature range does it cover?

Rated -40 °C minimum to 70 °C maximum operating.

What approvals does it carry for hazardous locations?

ATEX II 3 G Ex nA [ib Gb] IIC T4 Gc, FM Class I Division 2 Groups A B C D T4, and UL File E239877.

What are the intrinsic safety output parameters?

Uo 25.2 V max, Po 431 mW max. PTB test number Ex-96.D.2092X.

MPN
6AG1331-7RD00-2AB0