Siemens 6AG1332-5HF00-4AB0 — Analog Output Modules

Siemens 6AG1332-5HF00-4AB0 Analog Output Module, 8 Channels

MPN6AG1332-5HF00-4AB0

Siemens S7-300 analog output module, 8 channels, 24 V DC, bipolar voltage and current ranges, 40-pin front connector, active production.

$1,047.75Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

6AG1332-5HF00-4AB0 — Outputs
ParameterValue
Number of analog outputs8
Output range: -10 V to +10 VYes
Output range: 0 to 10 VYes
Output range: 1 V to 5 VYes
Output range: 0 to 20 mAYes
Output range: 4 to 20 mAYes
Output range: -20 mA to +20 mAYes
Load resistance, current outputs, max.500 Ω
Load resistance, voltage outputs, min.1 kΩ
Current output, no-load voltage, max.18 V
Voltage output, short-circuit current, max.25 mA
Voltage output, short-circuit protectionYes
Inductive load, current outputs, max.10 mH
Capacitive load, voltage outputs, max.1 µF
Cable length, shielded, max.200 m
6AG1332-5HF00-4AB0 — Performance
ParameterValue
Resolution (incl. sign, with overrange), max.12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit
Error, voltage output (rel. to output range)0.4 %
Error, current output (rel. to output range)0.5 %
Conversion time (per channel)0.8 ms
Settling time, resistive load0.2 ms
Settling time, inductive load0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH)
Settling time, capacitive load3.3 ms
6AG1332-5HF00-4AB0 — Power
ParameterValue
Rated value (DC)24 V
Power loss (typ.)6 W
Current consumption from backplane bus (5 V DC), max.100 mA
Current consumption from load voltage L+ (no load), max.340 mA
Reverse polarity protectionYes
6AG1332-5HF00-4AB0 — Diagnostics
ParameterValue
Diagnostics functionYes; Parameterizable
Diagnostic interrupt/alarmYes; Parameterizable
6AG1332-5HF00-4AB0 — Isolation
ParameterValue
Isolation: channels to backplane busYes
Isolation: between channelsNo
Isolation: channels to load voltage L+Yes
Isolation test voltage500 V DC
6AG1332-5HF00-4AB0 — Environmental
ParameterValue
Temperature, max.60 °C; = Tmax
Temperature, min.0 °C; = Tmin
6AG1332-5HF00-4AB0 — Mechanical
ParameterValue
Front connector required40-pin
Width40 mm
Height125 mm
Depth120 mm

Product details

Panel fit and channel count

The 6AG1332-5HF00-4AB0 is an 8-channel analog output module for the S7-300 family, drawing 40 mm of DIN-rail width and 125 mm height — sits in a standard S7-300 rack slot. It needs a 40-pin front connector (not included) and pulls 100 mA from the 5 V backplane bus plus 6 W typical from the 24 V DC field supply.

What the output ranges mean for the loop

Each channel covers the common industrial signal standards: voltage outputs from -10 V to +10 V, 0 to 10 V, and 1 V to 5 V; current outputs from 0 to 20 mA, 4 to 20 mA, and -20 mA to +20 mA. That bipolar current range is unusual on an S7-300 AO — it lets you drive ±20 mA into a valve or transducer without a separate signal conditioner. Minimum load for voltage outputs is 1 kΩ; maximum burden for current outputs is 500 Ω. Conversion time per channel is 0.8 ms — fast enough for closed-loop control on a hydraulic or pneumatic valve bank. Shielded cable run is rated up to 200 m before signal degradation becomes an issue.

What it replaces and what it doesn't

The 6AG1332-5HF00-4AB0 is the SIPLUS variant of the standard 6ES7332-5HF00-0AB0. The SIPLUS version adds a conformal coating rated for medial exposure — meaning it handles condensation, corrosive gases, and dust better than the standard module. Pin-compatible in the same S7-300 slot; the 40-pin front connector and wiring are identical. If your environment is clean and dry, the standard 6ES7 variant saves cost; if the panel sees humidity or aggressive atmospheres, the SIPLUS coating is the difference between a module that lasts and one that fails mid-shift.

Diagnostics and commissioning

Parameterizable diagnostics include group error (SF red LED) and per-channel diagnostic alarm — readable over the backplane bus. Reverse polarity protection on the 24 V DC supply prevents a swapped wire from killing the module. Isolation tested at 500 V DC between the bus and field circuits.

MPN