The Siemens 6AG1332-7ND02-4AB0 is a SIPLUS S7-300 analog output module providing four channels with selectable voltage or current outputs. The module operates across -40 °C to 70 °C, making it suited for uncontrolled environments or extended thermal ranges within a panel. Each channel supports 0 to 10 V, -10 V to +10 V, 0 to 20 mA, 4 to 20 mA, and ±20 mA ranges. A diagnostic alarm and red group-error LED (SF) indicate channel faults or supply loss. Conversion time per channel is 200 µs in standard mode; in isochronous mode it extends to 640 µs. Isolation between channels and backplane bus is tested at 1 500 V DC. Power draw from the backplane bus is 120 mA at 5 V DC typical, with a total module power loss of 3 W. Reverse polarity protection on the 24 V DC supply is included.
Sourcing & Compliance
UL approval is on file under number E239877. Additional agency marks include CE, KC, EAC (Gost-R), and RCM. RoHS/REACH compliance is implicit per Siemens SIPLUS documentation; the module carries CE marking as self-declared.
Integration Dimensions
With voltage outputs, the minimum load resistance is 1 kΩ. With current outputs, the maximum loop resistance is 500 Ω. Shielded cable length is limited to 200 m. Load response times per type: resistive 0.2 ms, inductive 0.5 ms, capacitive 3.3 ms.