Siemens 6AG1333-4BA00-7AA0
MPN6AG1333-4BA00-7AA0
Active
SIPLUS S7-1500 PM 1507 24V/8A based on 6EP1333-4BA00 with conformal coating, -40…+70 °C, stabilized power supply for SIMATIC S7-1500 input: 120/230 V AC output: 24 V DC/8 A
$402.59Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
| Parameter | Value |
|---|---|
| Fuse protection type | T 6.3 A/250 V (not accessible) |
| Type of electrical connection | Screw-/spring clamp connection |
| Type of the power supply network | 1-phase AC |
| Voltage curve at output | Controlled, isolated DC voltage |
| At rated input voltage 120 | 3.7 A |
| At rated input voltage 230 | 1.7 A |
| Output voltage at DC rated value | 24 V |
| On slow fluctuation of input voltage | 0.1 % |
| Relative overall tolerance of the voltage | 1 % |
| Product function output voltage adjustable | No |
| Behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
| At rated output voltage for rated value of the output current typical | 21 W |
All specifications+66 ▾
| Parameter | Value |
|---|---|
| Relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.1 % |
| At Short-Circuit during operation | 70 ms |
| Response value current limitation | 8.4 ... 9.6 A |
| Design of Short-Circuit protection | Electronic shutdown, automatic restart |
| On Short-Circuiting during the Start-Up | 70 ms |
| At Short-Circuit during operation typical | 35 A |
| Property of the output Short-Circuit proof | Yes |
| On Short-Circuiting during the Start-Up typical | 35 A |
| Current limitation of inrush current at 25 °C maximum | 62 A |
| Buffering time for rated value of the output current in the event of power failure minimum | 20 ms |
| Supplied active power typical | 192 W |
| Number of Parallel-Switched equipment resources for increasing the power | 2 |
| Line frequency | 45 ... 65 Hz |
| Depth of the enclosure | 129 mm |
| Width of the enclosure | 75 mm |
| Height of the enclosure | 147 mm |
| Product feature of the enclosure housing can be lined up | Yes |
| In horizontal mounting position during operation | -40 ... +70 °C; with natural convection |
| Installation altitude at height above sea level maximum | 6 000 m |
| Ambient condition relating to ambient temperature - air pressure - installation altitude | In case of operation at altitudes of 2000 - 6000 m above sea level: Output power derating of -7.5 %/1000 m or reduction of the ambient temperature by 5 K/1000 m |
| Removable terminal at input | Yes |
| Removable terminal at output | Yes |
| MTBF at 40 °C | 1 362 918 h |
| CE marking | Yes |
| Top | 40 mm |
| Left | 0 mm |
| Right | 0 mm |
| Bottom | 40 mm |
| 1 at AC | 85 ... 132 V |
| 2 at AC | 170 ... 264 V |
| Typical | 1.3 mA |
| At input | L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² |
| At output | L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² |
| Rated range | 0 ... 8 A |
| Rated value | 8 A |
| 1 rated value | 50 Hz |
| 2 rated value | 60 Hz |
| In the feeder | Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C |
| Initial value | Automatic range selection |
| Mounting | Can be mounted onto S7-1500 rail |
| I2t value maximum | 12 A²·s |
| Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 |
| 1 at AC rated value | 120 V |
| 2 at AC rated value | 230 V |
| Protection class IP | IP20 |
| Bridging of equipment | Yes |
| Efficiency in percent | 90 % |
| Response delay maximum | 1.5 s |
| For emitted interference | EN 55022 Class B |
| For interference immunity | EN 61000-6-2 |
| Load step 10 to 90% typical | 5 ms |
| Load step 90 to 10% typical | 5 ms |
| During storage and transport | -40 ... +85 °C |
| At output 1 at DC rated value | 24 V |
| For mains harmonics limitation | EN 61000-3-2 |
| Overvoltage overload capability | 2.3 × Vin rated, 1.3 ms |
| Design of input wide range input | No |
| On slow fluctuation of ohm loading | 0.1 % |
| Operating resource protection class | Class I |
| Design of the overvoltage protection | Additional control loop, limitation (closed loop control) at < 28.8 V |
| Display version for normal operation | LED green for 24 V OK; LED red for error; LED yellow for stand-by |
| Operating condition of the mains buffering | at Vin = 93/187 V |
| Galvanic isolation between input and output | Yes |
| Chemical resistance to commercially available cooling lubricants | Yes; incl. diesel and oil droplets in the air |
| Product conformity of the coating qualification and performance of electrical insulating compound for printed board assemblies according to IPC-CC-830A | Yes; Conformal Coating, Class A |
MPN
6AG1333-4BA00-7AA0