Skip to main content
Siemens 6AG1412-2EK06-2AB0 — Industrial PCs

Siemens 6AG1412-2EK06-2AB0 CPU, 244 Byte I/O, -40 to 70°C

MPN6AG1412-2EK06-2AB0

Siemens 6AG1412‑2EK06‑2AB0 CPU, S7‑400 family, 244 byte I/O, -40 to 70 °C, LAD/FBD/STL/SCL/GRAPH/CFC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

6AG1412-2EK06-2AB0 — Performance
ParameterValue
Memory typeRAM
Required slots1
6AG1412-2EK06-2AB0 — Display
ParameterValue
Display resolution1 ms
6AG1412-2EK06-2AB0 — Communication & I/O
ParameterValue
TypeSFB
6AG1412-2EK06-2AB0 — Electrical
ParameterValue
Power loss (typ.)5.5 W
6AG1412-2EK06-2AB0 — Mechanical
ParameterValue
Width25 mm
Height290 mm
Depth219 mm
Weight (approx.)750 g
6AG1412-2EK06-2AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Ambient temperature vs. altitude / pressureTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1412-2EK06-2AB0 — Approvals
ParameterValue
CE markYes

Product details

The 6AG1412-2EK06-2AB0 CPU requires a system power supply — 24 V DC direct feed is not supported. It operates from -40 to 70 °C ambient, making it the ruggedized S7-400 option. Process image is limited to 244 bytes each for input and output. Programmable in LAD, FBD, STL, SCL, GRAPH, and CFC, so existing S7-400 logic migrates without conversion. IRT support via the integrated PROFINET interface keeps jitter under 1 ms for isochronous applications. Failure monitoring (FM) is bounded by the number of slots and connections — plan the configuration with this ceiling in mind if you rely on FM for diagnostics.

Key constraints

The CPU does not accept a separate 24 V DC input; it draws power from the rails of a system power supply. Plan the rack power budget accordingly.

Programming and communications

Supports LAD, FBD, STL, SCL, GRAPH, and CFC programming languages, ensuring compatibility with a wide range of existing S7-400 project libraries. Integrated PROFINET interface with IRT for real-time communication. Also supports TCP/IP and UDP via loadable function blocks. MPI is available for bus connection to HMI or other CPUs. Eight RDREC, WRREC, and RDSYSST blocks each are available for data record handling and system status reads.

The module fits a standard S7-400 rack: 25 mm wide × 290 mm high × 219 mm deep. Routing is supported with the interface active.

Frequently asked questions

What is the FM (Failure Monitoring) limitation?

FM is limited by the number of slots and the number of connections. Plan your configuration accordingly.

Does this CPU support CFC (Continuous Function Chart)?

Yes, CFC is supported.

What compliance documentation is available?

The CPU carries a CE mark.

MPN