Skip to main content
Siemens 6AG1431-0HH00-4AB0 — PLC I/O & Expansion Modules

Siemens 6AG1431-0HH00-4AB0 Analog Input, 16 Ch, -40 to 70°C

MPN6AG1431-0HH00-4AB0
NRND

Siemens 6AG1431-0HH00-4AB0 analog input module, 16 channels for voltage/current measurement, 24 V supply for 2-wire transmitters, -40 to 70°C ambient.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

6AG1431-0HH00-4AB0 — I/O
ParameterValue
Analog inputs16
6AG1431-0HH00-4AB0 — Electrical
ParameterValue
Rated value (DC)24 V; Only required for supplying 2-wire transmitters
Max.70 °C
Power loss (typ.)2 W
Current consumption from backplane bus (5 V DC), max.100 mA
Current consumption from load voltage L+ (no load), max.400 mA; for 16 connected, fully controlled 2-wire transmitters
Reverse polarity protectionYes
Isolation test voltage500 V DC between bus and local ground
Isolation: between channelsNo
Isolation: channels to backplane busNo
Max. cable length, shielded200 m
6AG1431-0HH00-4AB0 — Performance
ParameterValue
Resolution incl. overrange (bit, with sign), max.13 bit
Diagnostics functionNo
6AG1431-0HH00-4AB0 — Environmental
ParameterValue
Min.-40 °C
6AG1431-0HH00-4AB0 — Mechanical
ParameterValue
Height290 mm
Width25 mm
Depth210 mm
Weight (approx.)500 g

Product details

Analog Input Module – 16 Channels, Industrial Temperature Range

The Siemens 6AG1431-0HH00-4AB0 is a 16-channel analog input module. It accepts voltage inputs up to ±10 V and current inputs up to ±20 mA (including 4-20 mA), with a 24 V DC output to power up to 16 two-wire transmitters. The module draws 100 mA from the 5 V backplane bus and dissipates 2 W typical. Isolation is tested at 500 V DC between the bus and local ground; there is no potential separation between channels or between channels and the backplane bus. Rated for ambient operation from -40 to 70 °C, the module fits applications in unheated panels, cold storage, or outdoor enclosures.

Width is 25 mm, height 290 mm, depth 210 mm – standard ET 200SP form factor, mounts on a DIN rail. The module supplies 24 V for 2-wire transmitters; note that no diagnostic function is present on the module. Input resistance varies by range: 50 Ω for current inputs (4-20 mA and ±20 mA), 100 kΩ for ±10 V and 1-5 V ranges, and 10 MΩ for the ±1 V range. Reverse polarity protection is built in. Shielded cable length is limited to 200 m maximum.

Frequently asked questions

What is the ambient temperature range?

Operating ambient is -40 to 70 °C.

Does the module include diagnostics or channel-to-channel isolation?

No. The module has no diagnostics function and no potential separation between channels or between channels and the backplane bus.

MPN
6AG1431-0HH00-4AB0