Siemens 6AG1436-2BA10-7AA0 — Industrial PCs

Siemens 6AG1436-2BA10-7AA0 SITOP Power Supply, 20 A

MPN6AG1436-2BA10-7AA0
Active

Siemens SITOP, 6AG1436-2BA10-7AA0, 20 A rated adjustable 24–28 V DC power supply, 91 % efficiency, IP20, DIN-rail mount.

$434.34Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1436-2BA10-7AA0 key specifications
ParameterValue
Type of signal at outputRelay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
Type of electrical connectionscrew-type terminals
Type of output voltage settingvia potentiometer; max. 480 W
Type of the power supply network3-phase AC
Voltage curve at outputControlled, isolated DC voltage
Adjustable output voltage24 ... 28 V
At rated input voltage 4001.2 A
At rated input voltage 5001 A
Output voltage at DC rated value24 V
On slow fluctuation of input voltage0.5 %
Relative overall tolerance of the voltage3 %
Product function output voltage adjustableYes

All specifications

6AG1436-2BA10-7AA0 additional specifications
ParameterValue
Behavior of the output voltage when switching onNo overshoot of Vout (soft start)
At rated output voltage for rated value of the output current typical47 W
Relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical3 %
At Short-Circuit during operation100 ms
Design of Short-Circuit protectionElectronic shutdown, automatic restart
On Short-Circuiting during the Start-Up100 ms
At Short-Circuit during operation typical35 A
Property of the output Short-Circuit proofYes
On Short-Circuiting during the Start-Up typical35 A
Current limitation of inrush current at 25 °C maximum36 A
Buffering time for rated value of the output current in the event of power failure minimum6 ms
Supplied active power typical480 W
Number of Parallel-Switched equipment resources for increasing the power2
Line frequency47 ... 63 Hz
Depth of the enclosure150 mm
Width of the enclosure90 mm
Height of the enclosure145 mm
Product feature of the enclosure housing can be lined upYes
In horizontal mounting position during operation-40 ... +60 °C; with natural convection
Installation altitude at height above sea level maximum6 000 m
Ambient condition relating to ambient temperature - air pressure - installation altitudeIn case of operation at altitudes of 2000 - 6000 m above sea level: Output power derating of -7.5 %/1000 m or reduction of the ambient temperature by 5 K/1000 m
MTBF at 40 °C500 000 h
CE markingYes
Top40 mm
Left0 mm
Right0 mm
Bottom40 mm
Typical1 mA
At inputL1, L2, L3, PE: 1 screw terminal each for 0.5 ... 4 mm² single-core/finely stranded
At output+, -: 2 screw terminals each for 0.2 ... 4 mm²
Rated range0 ... 20 A
Rated value20 A
1 rated value50 Hz
2 rated value60 Hz
In the feederRequired: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489-listed, DIVQ)
Initial value340 V
MountingSnaps onto DIN rail EN 60715 35x7.5/15
Full-Scale value550 V
I2t value maximum0.9 A²·s
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178, transformer acc. to EN 61558-2-16
Maximum rated value500 V
Minimum rated value400 V
Protection class IPIP20
Bridging of equipmentYes
Efficiency in percent91 %
Electrical accessoriesredundancy module, buffer module, selectivity module, DC UPS
For auxiliary contacts13, 14 (alarm signal): 1 screw terminal each for 0.05 ... 2.5 mm²
Mechanical accessoriesDevice identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20
Response delay maximum1.5 s
For emitted interferenceEN 55022 Class B
For interference immunityEN 61000-6-2
During storage and transport-40 ... +85 °C
Load step 100 to 50% typical2 ms
Load step 50 to 100% typical2 ms
At output 1 at DC rated value24 V
For mains harmonics limitationEN 61000-3-2
Design of input wide range inputYes
On slow fluctuation of ohm loading1 %
Operating resource protection classClass I
Design of the overvoltage protectionprotection against overvoltage in case of internal fault Vout < 35 V
Display version for normal operationGreen LED for 24 V OK
Operating condition of the mains bufferingat Vin = 400 V
Galvanic isolation between input and outputYes
Overcurrent overload capability in normal operationoverload capability 150 % Iout rated up to 5 s/min
Chemical resistance to commercially available cooling lubricantsYes; incl. diesel and oil droplets in the air
Product conformity of the coating qualification and performance of electrical insulating compound for printed board assemblies according to IPC-CC-830AYes; Conformal Coating, Class A

Product details

SITOP 6AG1436-2BA10-7AA0 at a glance

This Siemens SITOP power supply delivers a controlled, isolated 24–28 VDC adjustable output at a full-scale 20 A, with a rated range of 0–20 A and 91% efficiency at 400–500 VAC input (47–63 Hz). Galvanic isolation to EN 60950-1 and EN 50178 ensures safe low-voltage outputs; the unit carries CE marking and meets EN 55022 Class B for emissions and EN 61000-6-2 for immunity. MTBF is rated 500 000 h at 40 °C, with a typical current draw of 1 mA (max 3.5 mA).

Panel mounting and clearances

Snaps onto DIN-rail EN 60715 (35×7.5/15). Enclosure dimensions: width 90 mm, height 145 mm, depth 150 mm. Adequate airflow requires 40 mm clearance above and below the unit; side clearance is 0 mm — modules can be abutted in a row without spacing. Protection class IP20 — suitable for clean, dry control cabinets only.

Connections and accessories

Input (, L2, L3, PE) accepts 0.5–4 mm² single-core or finely stranded wire per screw terminal. Output (+/−) accepts 0.2–4 mm². A separate alarm relay (NO contact) is on terminals 13–14. Electrical accessories listed by the manufacturer include a redundancy module, buffer module, selectivity module, and DC UPS for extended hold-up or dual-feed configurations. The feeder circuit must be protected by a 3-pole miniature circuit breaker (6–16 A, characteristic C) or a Siemens 3RV circuit breaker (setting 3 A) per the spec.

This is an active, current-production part. No end-of-life or last-time-buy notice applies.

Frequently asked questions

What are the required clearances around this power supply?

Top and bottom clearance must be 40 mm; left and right clearance can be 0 mm — units can be mounted side-by-side without gaps.

What compliance markings does it carry?

CE marking is present. Emissions meet EN 55022 Class B; immunity meets EN 61000-6-2. Galvanic isolation is per EN 60950-1 and EN 50178.

How do I source this part?

It is a standard active stock item. Submit an RFQ for current lead time and pricing; we can quote firm quantities against your delivery schedule.