Skip to main content
Siemens 6AG1507-0RA00-7AB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1507-0RA00-7AB0 SIPLUS PS, 60W, -40…70°C

MPN6AG1507-0RA00-7AB0
Active

Siemens SIPLUS S7-1500 PS 1507 60W system power supply, 6AG1507-0RA00-7AB0, for backplane bus, -40…+70 °C, conformal coating.

$643.89Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1507-0RA00-7AB0 — Electrical
ParameterValue
Rated value (DC)120 V; 230 V
Permissible range, lower limit (DC)88 V
Permissible range, upper limit (DC)300 V
Short-circuit protectionYes
6AG1507-0RA00-7AB0 — Environmental
ParameterValue
Installation altitude, max.2 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
6AG1507-0RA00-7AB0 — Mechanical
ParameterValue
Width70 mm
Height147 mm
Depth129 mm
Weight (approx.)600 g

Product details

System power supply for S7-1500

The Siemens 6AG1507-0RA00-7AB0 is a SIPLUS S7-1500 power supply delivering 60 W to the backplane bus, rated for -40 to +70 °C with conformal coating for harsh environments. It accepts 120 V or 230 V AC/DC input (permissible range 85–264 V AC, 88–300 V DC) and provides short-circuit protection, redundancy capability, and an uprating feature for increased reliability. The unit occupies DIN-rail space: 70 mm wide, 147 mm high, 129 mm deep, IP20 rated, with isolation tested at 2 500 V DC.

Temperature range and output derating

The full -40 to +70 °C operating range suits outdoor cabinets, cold storage, or high-heat process areas. Derating also applies to altitude: the rating holds from -1 000 m to +2 000 m at standard atmospheric pressure. Up to 2 000 m, no additional margin is required. The supply maintains 20 ms ride-through on mains failure, enough for most PLC hold-up capacitors to bridge through a cycle drop.

Active production — no obsolescence risk

It is based on the standard S7-1500 power supply with added conformal coating and extended temperature range.

Frequently asked questions

What is the maximum operating temperature?

70 °C. Above 60 °C the backplane power output derates from 60 W to 30 W.

What is the minimum operating temperature?

-40 °C, with startup from -25 °C.

Does this power supply replace the standard 6ES7507-0RA00-0AB0?

It is a hardened version of that unit with conformal coating and wider temperature range. In a clean, 0–60 °C panel the standard unit is a functional equivalent; for extreme temperatures or coating requirements, this SIPLUS variant is the correct choice.

MPN
6AG1507-0RA00-7AB0