Skip to main content
Siemens 6AG1512-1DK01-2AB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1512-1DK01-2AB0 S7-1500 CPU, 32 kB I/O, IRT, MRP

MPN6AG1512-1DK01-2AB0

Siemens 6AG1512-1DK01-2AB0 S7-1500 CPU, 32 kB I/O image, PROFINET IRT with MRP, hardware clock, DCP/DNS, 100x117x75 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1512-1DK01-2AB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)48 ns
Execution time, word operations (typ.)58 ns
Execution time, floating-point arithmetic (typ.)307 ns
Size, max.16 kbyte
6AG1512-1DK01-2AB0 — I/O
ParameterValue
Input data area32 kbyte; All inputs are in the process image
Output data area32 kbyte; All outputs are in the process image
6AG1512-1DK01-2AB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6AG1512-1DK01-2AB0 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)0.6 A
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)5.6 W
6AG1512-1DK01-2AB0 — Environmental
ParameterValue
Installation altitude, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)60 °C; = Tmax
6AG1512-1DK01-2AB0 — Mechanical
ParameterValue
Width100 mm
Height117 mm
Depth75 mm
Weight (approx.)310 g

Product details

Fit and features

The Siemens 6AG1512-1DK01-2AB0 CPU has a 32 kbyte input and 32 kbyte output process image, supports PROFINET IRT and MRP manager/client, and MRPD (requires IRT). The hardware clock synchronizes time stamps across the network. No PROFIsafe integration on this CPU, so it is not used as the safety controller in a SIL-rated zone. Use a separate F-CPU or F-module for safety functions. The wide protocol stack includes MODBUS TCP, HTTP/HTTPS, SNMP, LLDP, DHCP/DNS, and UDP, which simplifies integration into mixed-vendor networks. The I2t rating of 0.14 A²·s is relevant for coordination of the internal power supply path when designing the panel selective protection scheme. For installations with high ambient temperatures, the 100 x 117 x 75 mm footprint fits standard DIN-rail spacing; ensure clearance above and below for ventilation.

Sourcing and fit confirmation

This order code is the industrial-optimized variant (6AG1 prefix). It shares the same mounting and form factor as the standard 6ES7 variants but includes integrated PID temperature and 3-step valve controllers. Quote the exact code for your BOM line — we procure against RFQ.

Frequently asked questions

Does this CPU support PROFIsafe?

No, PROFIsafe is not supported on the 6AG1512-1DK01-2AB0. Use a separate safety CPU for SIL-rated functions.

What is the process image size?

It has 32 kbyte input and 32 kbyte output process images, all inputs and outputs included.

What industrial protocols are supported?

PROFINET IRT with MRP, MRPD, MODBUS TCP, HTTP/HTTPS, SNMP, LLDP, DHCP, DNS, and UDP.

What is the I2t rating for?

0.14 A²·s is the I2t value for the internal power path, used for selective coordination in the panel protection scheme.

MPN
6AG1512-1DK01-2AB0