Skip to main content
Siemens 6AG1512-1SK00-2AB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1512-1SK00-2AB0 CPU 1512SP-1 PN, IRT, MRP, MODBUS

MPN6AG1512-1SK00-2AB0

Siemens SIMATIC S7-1500, CPU 1512SP-1 PN, 100 x 117 x 75 mm, with PROFINET IRT, MRP, MODBUS TCP, web server.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1512-1SK00-2AB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)48 ns
Execution time, word operations (typ.)58 ns
Execution time, floating-point arithmetic (typ.)307 ns
Size, max.300 kbyte
6AG1512-1SK00-2AB0 — I/O
ParameterValue
Input data area32 kbyte; All inputs are in the process image
Output data area32 kbyte; All outputs are in the process image
6AG1512-1SK00-2AB0 — Programming
ParameterValue
Programming language: FBDYes; incl. failsafe
Programming language: LADYes; incl. failsafe
Programming language: SCLYes
6AG1512-1SK00-2AB0 — Electrical
ParameterValue
Current consumption (rated)0.6 A
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)5.6 W
6AG1512-1SK00-2AB0 — Mechanical
ParameterValue
Width100 mm
Height117 mm
Depth75 mm
Weight (approx.)310 g
6AG1512-1SK00-2AB0 — Environmental
ParameterValue
Operating temperature, min. (horizontal mounting)-25 °C; = Tmin
Operating temperature, max. (horizontal mounting)60 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m)

Product details

The 6AG1512-1SK00-2AB0: FBD and LAD programming languages include failsafe logic, so you can implement safety-rated functions without a dedicated safety CPU. The hardware clock holds time, and forcing is available for commissioning overrides.

Integrated connectivity and redundancy

Three communication highlights separate this CPU from a plain PROFINET controller. First, IRT (isochronous real-time) delivers deterministic cyclic data for motion axes. Second, MRP (media redundancy protocol) lets this unit act as redundancy manager in a ring of up to 50 devices – no extra switch needed. Third, MODBUS TCP is built in, so you talk to drives, HMIs, or third-party sensors without a gateway module. UDP, TCP/IP, and LLDP round out the stack.

Memory and processing

The process image handles 32 kbyte for inputs and 32 kbyte for outputs – all variables map into the image unless you explicitly bypass it. Program memory is 300 kbyte (code + data blocks). The CPU supports S7 routing, which simplifies programming across multiple subnets. Forcing outputs is enabled, a time-saver during startup when you need to bypass sensor interlocks temporarily.

Physical fit and sourcing

Dimensions are 100 mm wide, 117 mm high, and 75 mm deep – the standard ET 200SP housing. For sourcing: this CPU is an active current-design part from Siemens; lead times are met through our supply chain.

Frequently asked questions

What communication interfaces does the CPU 1512SP-1 PN support?

The CPU has one PROFINET port that supports IRT (isochronous real-time), MRP redundancy manager/client (up to 50 devices in the ring), MODBUS TCP, UDP, TCP/IP, HTTP/HTTPS web server, LLDP, and SNMP. DHCP is not supported.

What are the physical dimensions of the 6AG1512-1SK00-2AB0?

Width 100 mm, height 117 mm, depth 75 mm. It fits the standard ET 200SP profile for DIN-rail mounting.

Does this CPU support failsafe programming?

Yes, both LAD (ladder diagram) and FBD (function block diagram) include failsafe instructions, allowing safety logic within the same CPU without a separate safety controller.

MPN
6AG1512-1SK00-2AB0