Skip to main content
Siemens 6AG1513-1AL01-2AB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1513-1AL01-2AB0 CPU, -40 to 70°C, MRP

MPN6AG1513-1AL01-2AB0

Siemens S7-1500 SIPLUS CPU 6AG1513-1AL01-2AB0, -40 to 70°C, MRP redundancy manager, web server with HTTPS.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1513-1AL01-2AB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)40 ns
Execution time, word operations (typ.)48 ns
Execution time, floating-point arithmetic (typ.)256 ns
Size, max.16 kbyte
6AG1513-1AL01-2AB0 — I/O
ParameterValue
Input data area32 kbyte; All inputs are in the process image
Output data area32 kbyte; All outputs are in the process image
6AG1513-1AL01-2AB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6AG1513-1AL01-2AB0 — Electrical
ParameterValue
Current consumption (rated)0.7 A
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)5.7 W
6AG1513-1AL01-2AB0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin; Startup @ -20 °C
Operating temperature, max. (horizontal mounting)60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1513-1AL01-2AB0 — Mechanical
ParameterValue
Width35 mm
Height147 mm
Depth129 mm
Weight (approx.)430 g

Product details

Field-fit for cold and hot environments

That means it's the version you specify for freezer lines, desert switchgear, or anywhere the panel sees thermal extremes. Below 0 °C the display legibility drops, but the logic and I/O remain functional; plan remote monitoring if the panel is subzero during operation. Integrated MRP redundancy manager handles rings up to 50 devices without an extra module. Saves one slot and the associated wiring if you're building a redundant ring. Compatible with standard S7-1500 MRP clients.

Built-in web server and communication stack

HTTP and HTTPS web server with standard and user-defined pages — no additional license or HMI hardware for basic monitoring. HTTPS is factory-enabled, covering modern security policies. controller is integrated for valve applications, with auto-tuning available in STEP 7 V12 SP1 and later. Supports MODBUS TCP, TCP/IP, UDP, and SNMP. No DHCP on this unit — set a fixed IP or assign via the controller program. PROFINET IO with IRT is supported, and S7 routing allows cross-network programming.

Sourcing reality: genuine part, different passport

This order code is the extended-temperature variant, often stocked in European or APAC distribution. Same part, different passport — it's genuine Siemens, but may carry regional packaging and a local warranty that doesn't always transfer out of region. Let me be transparent: if your plant requires an official Siemens service contract, the standard-temperature sibling may be a cleaner path. But for cold-environment builds, this is the correct spec.

Frequently asked questions

Does the 6AG1513-1AL01-2AB0 support DCP?

Yes, DCP (Discovery and Configuration Protocol) is supported, allowing integration into PROFINET networks using Siemens configuration tools.

Does it support FBD (Function Block Diagram) programming?

Yes, FBD is supported, along with LAD, STL, SCL, and GRAPH (as of STEP 7 V12 SP1).

What is the operating temperature range?

The CPU is rated from -40 °C to 70 °C. Note that below 0 °C the display legibility may be reduced, but the device remains operational.