Siemens 6AG1515-2RM00-7AB0 CPU 1515-2 PN SIPLUS -40 to 70°C

MPN6AG1515-2RM00-7AB0

Siemens SIPLUS ET 200SP CPU 1515-2 PN, order code 6AG1515-2RM00-7AB0, -40 to 70 °C, 32 kbyte process image, MRP Manager Auto.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1515-2RM00-7AB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)60 ns
Execution time, word operations (typ.)72 ns
Execution time, floating-point arithmetic (typ.)384 ns
Size, max.16 kbyte
6AG1515-2RM00-7AB0 — I/O
ParameterValue
Input data area32 kbyte; All inputs are in the process image
Output data area32 kbyte; All outputs are in the process image
6AG1515-2RM00-7AB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6AG1515-2RM00-7AB0 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)0.8 A
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)6.3 W
6AG1515-2RM00-7AB0 — Environmental
ParameterValue
Installation altitude, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Temperature, min.-40 °C
Temperature, max.70 °C
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost); start-up @ -20 °C
Operating temperature, max. (horizontal mounting)70 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off
Ambient temperature vs. altitude/pressure deratingRestrictions for installation altitudes > 2 000 m, see entry ID: 109763260
6AG1515-2RM00-7AB0 — Mechanical
ParameterValue
Width105 mm
Height147 mm
Depth129 mm
Weight (approx.)1 100 g

Product details

SIPLUS CPU 1515‑2 PN – field note for the integrator

The 6AG1515-2RM00-7AB0: Process image is 32 kbyte each for inputs and outputs — enough for a medium IO station without splitting the rack. MRP Manager Auto is permanently set in TIA; the CPU handles ring recovery for up to 50 nodes (16 recommended) with no extra programming. Supported languages: LAD, FBD, SCL, STL. CFC and GRAPH are not available on this CPU — if batch/sequential control is in the project, the program has to be written in SCL or structured text.

Frequently asked questions

What is the operating temperature range of the 6AG1515-2RM00-7AB0?

Rated from -40 °C to 70 °C. At sub‑zero temperatures the display legibility may be restricted, and dynamic content updates may be slower.

What programming languages are supported?

LAD, FBD, SCL, and STL. CFC and GRAPH are not supported on this CPU.