6AG1521-1FH00-7AA0 — Inputs
ParameterValue
Number of digital inputs16; > +60 °C, number of simultaneously controllable inputs max. 8
2-wire sensor supportYes
6AG1521-1FH00-7AA0 — Electrical
ParameterValue
Input voltage at signal "1"79V AC to 264V AC
Input voltage at signal "0"0V AC to 40V AC
Input current at signal "1" (typ.)11 mA; At 230 V AC/50 Hz and 6.5 mA at 120 V AC/50 Hz
Power loss (typ.)4.9 W
Permissible quiescent current, 2-wire sensor, max.2 mA
Cable length, unshielded, max.600 m
Cable length, shielded, max.1 000 m
6AG1521-1FH00-7AA0 — Timing
ParameterValue
Input delay 0 to 1, max.25 ms
Input delay 1 to 0, max.25 ms
Input delay, parameterizable valuesNo
6AG1521-1FH00-7AA0 — Environmental
ParameterValue
Max. ambient temperature, horizontal installation70 °C; = Tmax; > +60 °C number of simultaneously controllable inputs max. 8
6AG1521-1FH00-7AA0 — Diagnostics & Isolation
ParameterValue
Short-circuit (NAMUR sensor)No
Diagnostic alarmNo
Hardware interrupt supportNo
Isolation between channelsNo
Isolation between channels and backplane busYes
Isolation test voltage2 500 V DC
Channels per isolated group4
6AG1521-1FH00-7AA0 — Mechanical
ParameterValue
Depth129 mm
Height147 mm
Width35 mm
6AG1521-1FH00-7AA0 — Specifications
ParameterValue
Rated value (AC)230 V; 120/230 V AC (47 Hz to 63 Hz)

Product details

The 6AG1521-1FH00-7AA0: 16-channel AC input module for the S7-1500, SIPLUS-coated for condensation and extended temperature. Accepts 120/230 V AC (47 Hz to 63 Hz) without jumpers; typical current draw per channel is 11 mA at 230 V AC. Module powers up in 500 ms — useful for fast restarts after power flickers. Rated operating range: -40°C to +70°C when mounted horizontally, -40°C to +40°C vertically. Above +60°C horizontal, the number of simultaneously controllable inputs drops from 16 to 8 — factor that into your thermal budget.

Isolation, wiring, diagnostics

Channel-to-backplane isolation tested at 2 500 V DC; between-channel groups of 4 are isolated for 250 V AC. Shielded cable runs up to 1 000 m, unshielded up to 600 m. No short-circuit detection, no wire-break alarm, no diagnostic alarm. Front-panel LEDs: green RUN, red ERROR, green per-channel status, red module diagnostic indicator. Status updates within 25 ms on rising and falling edges.

MPN