Siemens 6AG1522-1BH00-7AB0 SIPLUS DO Module
MPN6AG1522-1BH00-7AB0
***Spare Part*** ***Spare part*** SIPLUS S7-1500 DO 16x DC 24V -25...+70°C with conformal coating based on 6ES7522-1BH00-0AB0. Digital "output module ""16 channels in" "groups of 8;"" ""4 A per group;""" "diagnostics; substitute value"
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Outputs
| Parameter | Value |
|---|---|
| Digital outputs | 16; > +60 °C Number of simultaneously controllable outputs max. 8x 0.5 A, max. total current per group 2 A |
| Output type | Transistor |
Electrical
| Parameter | Value |
|---|---|
| Rated value (DC) | 24 V |
| Output current, resistive load, max. | 100 Hz |
| Output current at signal "1" (rated) | 0.5 A |
| Output current, max. per circuit / per module | 0.5 A |
| Total output current per module, max. | 8 A; see additional description in the manual |
| Permissible range, upper limit (DC) | 28.8 V |
| Permissible range, lower limit (DC) | 20.4 V |
| Output voltage at signal "1" (min.) | L+ (-0.8 V) |
| Residual current at signal "0", max. | 0.5 mA |
| Power dissipation (typ.) | 2 W |
| Inductive shutdown voltage clamp | L+ (-53 V) |
| Load resistance, upper limit | 12 kΩ |
| Load resistance, lower limit | 48 Ω |
| Isolation between channels | No |
| Isolation between channels and backplane bus | Yes |
| Isolation, channels in groups of | 8 |
| Isolation test voltage | 707 V DC (type test) |
Protection & Diagnostics
| Parameter | Value |
|---|---|
| Short-circuit protection | Yes; Clocked electronically |
| Reverse polarity protection | Yes; through internal protection with 7 A per group |
| Diagnostics function | Yes |
| Diagnostic alarm | Yes |
| Short-circuit response threshold (typ.) | 1 A |
| Short-circuit detection | Yes |
| Wire-break detection | No |
| Redundant load control | Yes |
| Output can drive a digital input | Yes |
Performance
| Parameter | Value |
|---|---|
| Output switching delay 0 to 1, max. | 100 µs |
| Output switching delay 1 to 0, max. | 500 µs |
| Switching frequency, inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 |
| Switching frequency, lamp load, max. | 10 Hz |
Environmental
| Parameter | Value |
|---|---|
| Operating temperature, horizontal mount, max. | 70 °C; = Tmax; > +60 °C Number of simultaneously controllable outputs max. 8x 0.5 A, max. total current per group 2 A |
| Operating temperature, horizontal mount, min. | -25 °C; = Tmin |
Mechanical & Connection
| Parameter | Value |
|---|---|
| Cable length, unshielded, max. | 600 m |
| Cable length, shielded, max. | 1 000 m |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weight (approx.) | 230 g |
MPN
6AG1522-1BH00-7AB0