Specifications

6AG1531-7KF00-7AB0 — Inputs & Signal Ranges
ParameterValue
Number of analog inputs8; > +60 °C max. 2x ±20 mA or 4x ±10 V or 4x RTD permissible
Input range: 0 to 20 mAYes
Input range: 4 to 20 mAYes
Input range: -10 to +10 VYes
Input range: -5 to +5 VYes
Input range: -80 to +80 mVYes
Input range: 0 to 600 OhmYes
RTD type: Pt100Yes; Standard/climate
RTD type: Pt200Yes; Standard/climate
Current measurement: 2-wire transducerYes
Current measurement: 4-wire transducerYes
Input resistance (0 to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input resistance (4 to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input resistance (-10 to +10 V)100 kΩ
Permissible input voltage, max. (destruction limit)28.8 V
Permissible input current, max. (destruction limit)40 mA
Max. shielded signal cable length800 m; for U/I, 200 m for R/RTD, 50 m for TC
6AG1531-7KF00-7AB0 — Measurement Performance
ParameterValue
Resolution (bit incl. sign), max.16 bit
Temperature measurement error (±)0.005 %/K; With TC type T 0.02 ± % / K
Voltage measurement error (±)0.1 %
Current measurement error (±)0.1 %
Common-mode interference suppression, min.60 dB
Common-mode voltage, max.10 V
6AG1531-7KF00-7AB0 — Diagnostics & Monitoring
ParameterValue
Wire-break detectionYes; Only for 1 to 5 V, 4 to 20 mA, TC, R, and RTD
Diagnostic alarmYes
Diagnostics functionYes
Limit value alarmYes; two upper and two lower limit values in each case
Supply voltage monitoringYes
6AG1531-7KF00-7AB0 — Isolation
ParameterValue
Isolation: channels to backplane busYes
Isolation: between channelsNo
Isolation test voltage707 V DC (type test)
6AG1531-7KF00-7AB0 — Power
ParameterValue
Rated value (DC)24 V
Power loss, typ.2.7 W
6AG1531-7KF00-7AB0 — Environmental
ParameterValue
Operating temperature, horizontal mounting, max.70 °C; = Tmax
Operating temperature, horizontal mounting, min.-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, vertical mounting, max.40 °C; = Tmax
Operating temperature, vertical mounting, min.-40 °C; = Tmin
6AG1531-7KF00-7AB0 — Mechanical
ParameterValue
Width35 mm
Height147 mm
Depth129 mm
Weight, approx.200 g

Product details

SIPLUS analog input for S7-300 – sensor coverage and precision

Siemens SIPLUS 6AG1531-7KF00-7AB0 analog input module (current) accepts PTC, Pt100, Ni100, Pt1000, Ni1000, and thermocouples B/E/J/K/N/R/S/T. Voltage ranges: -10 V to +10 V, -20 mA to +20 mA, 0-20 mA, 4-20 mA, -50 mV to +50 mV. For high-speed machine tool thermal mapping, the additional error at 2.5 ms integration time is the figure to watch: ±1 K on type K thermocouple, ±0.08 K on Pt100 climate, or ±0.02 % of voltage span on the ±250 mV range. That holds the deterministic repeatability needed for closed-loop thermal compensation. Wire-break detection is active on 1-5 V, 4-20 mA, thermocouple, resistance, and RTD signals – a standard diagnostic for line-down fault isolation.

Integration – dimensions, wiring, and signal conditioning

Maximum shielded cable lengths: 800 m for voltage/current inputs, 200 m for resistance and RTD, 50 m for thermocouples. Run the TC wiring short to keep the cold junction stable; shield grounded at the panel end only. Status indication via green RUN LED and red ERROR LED; I&M data up to I&M3 for asset tracking during BOM freeze audits.

Lifecycle stage is current; no end-of-life notice issued.

Frequently asked questions

Does this module support PTC sensors?

Yes, PTC sensor support is confirmed.

What is the physical depth of the module?

129 mm depth, plus DIN-rail clearance.

MPN