Skip to main content
Siemens 6AG1540-1AD00-7AA0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1540-1AD00-7AA0 SIPLUS S7-1500 CP RS-232, -40..70

MPN6AG1540-1AD00-7AA0
NRND

Siemens SIPLUS S7-1500, CP 1540-1 RS-232 communication module, 6AG1540-1AD00-7AA0, -40 to 70 °C, 19.2 kbit/s, 35 mA from backplane bus.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

6AG1540-1AD00-7AA0 — I/O
ParameterValue
Input data area8 byte
6AG1540-1AD00-7AA0 — Electrical
ParameterValue
Current consumption (rated)35 mA; From the backplane bus
Power loss (typ.)0.6 W
6AG1540-1AD00-7AA0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
Operating temperature, max. (horizontal mounting)70 °C
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1540-1AD00-7AA0 — Mechanical
ParameterValue
Width35 mm
Height147 mm
Depth127 mm
Weight (approx.)0.22 kg

Product details

RS-232 serial communication for S7-1500

The 6AG1540-1AD00-7AA0: It's designed for extended temperature range: horizontal installation from -40 to 70 °C; vertical up to 40 °C. Startup from -25 °C. This makes it suitable for harsh environments. The module draws 35 mA from the backplane bus and dissipates 0.6 W typical. It has a 2 kbyte buffer for telegrams, supports fast startup, and provides diagnostic alarms plus wire-break detection.

Mounts on the S7-1500 mounting rail. Width is 35 mm. Powered from the backplane bus. The RS-232 port is on the front, with green/yellow LEDs for TxD, RxD, and RUN.

Frequently asked questions

What is the maximum ambient temperature for this module?

Horizontal installation supports up to 70 °C; vertical installation supports up to 40 °C.

What is the minimum startup temperature?

The module can start up from -25 °C and operate down to -40 °C.

MPN