Siemens 6DL1131-6BH00-0PH1
MPN6DL1131-6BH00-0PH1
Active
SIMATIC ET 200SP HA, digital input module, DI 16X24VDC HA, suitable for terminal block H1, M1, color code CC01, channel diagnostics
$495.30Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Configurable from STEP 7 TIA Portal version | V16 |
| Firmware version | V1.0 |
Communication
| Parameter | Value |
|---|---|
| I&M data support | Yes; I&M0 to I&M3 |
| Diagnostics function | Yes |
Electrical
| Parameter | Value |
|---|---|
| Rated value (DC) | 24 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Current consumption, max. | 120 mA; without sensor supply |
| Power loss (typ.) | 3.6 W; Maximum value (taking the max. encoder current and the max. operating voltage into account) |
| Reverse polarity protection | Yes |
| Short-circuit protection | Yes; electronic (response threshold 0.7 A to 1.3 A; for IO redundancy up to 2.6 A) Ensure sufficient low-resistance cable routing to the sensor/actuator in order to attain the response threshold. Depending on the cable cross-section used, there may be constraints regarding the usable length of cable |
| Isolation test voltage | 1 500 V DC/1 min, type test |
Environmental
| Parameter | Value |
|---|---|
| Operating temperature, horizontal install, min. | -40 °C |
| Operating temperature, horizontal install, max. | 70 °C |
| Operating temperature, vertical install, max. | 60 °C |
| Operating temperature, vertical install, min. | -40 °C |
Mechanical
| Parameter | Value |
|---|---|
| Width | 22.5 mm |
| Height | 115 mm |
| Depth | 138 mm |
MPN
6DL1131-6BH00-0PH1