Skip to main content
Siemens 6ED1052-1HB08-0BA0 — PLCs (Programmable Logic Controllers)

Siemens 6ED1052-1HB08-0BA0 LOGO! 24RCE Logic Module, -40..70

MPN6ED1052-1HB08-0BA0
Active

Siemens LOGO! 24RCE logic module, 6ED1052-1HB08-0BA0, 24V AC/DC supply, 8 digital inputs, 4 relay outputs, 400-block program memory, integrated display, Ethernet, web server, 480h power reserve, -40 to 70 °C, 4 SU wide.

$142.00 – $403.25Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ED1052-1HB08-0BA0 — I/O
ParameterValue
Digital inputs8
Digital outputs4; Relays
6ED1052-1HB08-0BA0 — Electrical
ParameterValue
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Short-circuit protectionNo; external fusing necessary
6ED1052-1HB08-0BA0 — Environmental
ParameterValue
Temperature, min.-40 °C
Temperature, max.70 °C
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m)
6ED1052-1HB08-0BA0 — Mechanical
ParameterValue
Width71.5 mm
Height90 mm
Depth60 mm

Product details

What this LOGO! variant gives you

This is the 24V AC/DC version of the LOGO! 24RCE (6ED1052-1HB08-0BA0), the current-generation logic module with onboard display, Ethernet, and integrated web server. It runs off 24 V AC or 24 V DC (permissible range 20.4 to 28.8 V DC, 47 to 63 Hz AC). The power supply doesn't care which flavour you feed it, but the inputs need a clean 24 V level. Memory capacity is 400 blocks, function-specific — enough for moderate sequences, pump alternation, or small HVAC schedules. The 480-hour power reserve holds the program and retentive data across a weekend outage without a battery. Rated -40 to 70 °C, IP20, mounts on 35 mm DIN rail at 4 spacing units wide.

Rated -40 to 70 °C; the 1MD00-0BA7 is limited to 0–55 °C. Memory also differs: 400 blocks here vs 333 on the 1MD00-0BA7. If your program already compiles under 333 blocks, that's not a factor; if you need headroom, the 24RCE gives extra capacity.

Requires external short-circuit protection on the relay outputs — the module does not provide integral fusing. Use a suitably rated breaker or fuse on each output circuit.

Earth the DIN rail if used in a metal enclosure. Digital inputs are 8 total, no analog mixing — this is the pure 24V input version. Relay outputs rated 10 A resistive, 3 A inductive. For inductive loads (contactors, solenoids), add a free-wheel diode across the load or an RC snubber at the relay contacts; the 3 A inductive rating already accounts for a moderate inrush, not sustained arcs. Ethernet port is on-board; configure via LOGO! Soft Comfort V8 or higher. The web server serves custom pages for status dashboards. Use a standard microSD card for program backup or data logging.

MPN
6ED1052-1HB08-0BA0