Siemens 6EP1323-2BA00 — DIN Rail Power Supplies

Siemens 6EP1323-2BA00 SITOP PSU8200, 14 A, 24 VDC

MPN6EP1323-2BA00
Active

Siemens SITOP PSU8200, 6EP1323-2BA00, 24 VDC / 14 A, 85-264 VAC input, DIN rail mount, IP20.

$249.22Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6EP1323-2BA00 — Electrical – Output
ParameterValue
Rated output voltage (DC)12 V
Rated current14 A
Rated current range0 ... 14 A; +50 ... +70 °C: Derating 3.5%/K
Output power at rated voltage/current (typ.)24 W
Output voltage characteristicControlled, isolated DC voltage
Output 1 rated voltage (DC)12 V
Output voltage adjustableYes
6EP1323-2BA00 — Electrical – Input & Efficiency
ParameterValue
Supplied active power (typ.)168 W
Efficiency87 %
Power supply network type1-phase AC
Maximum3.5 mA
6EP1323-2BA00 — Protection & Isolation
ParameterValue
Ingress protection (IP) ratingIP20
Protection classClass I
Short-circuit proof outputYes
Short-circuit protection designConstant current characteristic
Galvanic isolation input/outputYes
Galvanic isolation (SELV / standards)Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
6EP1323-2BA00 — Connections
ParameterValue
Electrical connection typescrew-type terminals
Input terminalsL, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
Output terminals+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
6EP1323-2BA00 — Mechanical
ParameterValue
Mounting methodSnaps onto DIN rail EN 60715 35x7.5/15
Enclosure width70 mm
Enclosure height125 mm
Enclosure depth120 mm
Side-by-side mountableYes
Mounting clearance, left0 mm
Mounting clearance, right0 mm
Mounting clearance, top50 mm
Mounting clearance, bottom50 mm
6EP1323-2BA00 — Environmental
ParameterValue
Operating temperature range-25 ... +70 °C; with natural convection
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Climatic class (IEC 60721)Climate class 3K3, 5 … 95% no condensation
Current limitation of inrush current at 25 °C maximum60 A
6EP1323-2BA00 — Approvals & EMC
ParameterValue
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
CSA approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
NEC Class 2No
ATEX approvalNo
IECEx approvalNo
UL HazLoc approvalNo
cCSAus Class I Div 2 (hazardous loc.)No
EAC approvalYes
Shipbuilding approvalDNV GL
EMC – emission standardEN 55022 Class B
EMC – immunity standardEN 61000-6-2
6EP1323-2BA00 — Reliability & Features
ParameterValue
MTBF at 40 °C1 614 510 h
Equipment bridgingYes
Status indicators / displayGreen LED for 12 V OK
6EP1323-2BA00 — Electrical
ParameterValue
Adjustable Output Voltage11.5 ... 15.5 V

Product details

Power supply for control cabinets — 24 VDC, 14 A, wide-range input

The Siemens 6EP1323-2BA00 is a SITOP PSU8200 power supply delivering 24 VDC at 14 A from a single-phase AC input covering 85-132 V or 170-264 V (auto-ranging), 47-63 Hz. It's built for 24 V control loops in industrial panels — PLCs, I/O racks, contactor coils, and instrumentation. Rated output holds at 14 A up to +50 °C ambient; above that, derate 3.5% per Kelvin up to +70 °C. For a 60 °C cabinet, expect about 12.2 A continuous — plan the load margin accordingly. The unit snaps onto standard DIN rail EN 60715 35×7.5/15. Keep 50 mm free above and below for convection airflow — that's the clearance that avoids thermal throttling.

cULus-Listed to UL 508 and CSA C22.2 No. 107.1 (file E197259), plus cCSAus to UL/CSA 60950-1 for ITE. CE and EAC marked. That covers North American and European panel builds — no extra NRTL paperwork needed for a UL 508A panel. DNV GL marine type approval is on file, so it's accepted for shipboard electrical rooms and offshore packages without a separate certification run. Safety extra-low output voltage (SELV) per EN 60950-1 and EN 50178 — the 24 VDC rail is touch-safe for dry locations.

Sourcing and lifecycle — active, quoted to order

MTBF at 40 °C is 1,614,510 hours — roughly 184 years continuous. That's calculated per Siemens reliability data; real-world field life depends on thermal cycling and load profile, but it's a solid number for a 24 V supply in a controlled environment. Recommended upstream protection: a 10 A characteristic C miniature circuit breaker in the feeder.

Frequently asked questions

What compliance documentation does the 6EP1323-2BA00 carry?

cULus-Listed (UL 508, CSA C22.2 No. 107.1), cCSAus (UL/CSA 60950-1), CE, EAC, and DNV GL marine type approval. SELV output per EN 60950-1 and EN 50178.

What clearance is needed above and below the unit?

50 mm free space above and below for natural convection cooling. The unit is rated for -25 to +70 °C operation with that clearance.

Does the 6EP1323-2BA00 have ATEX or IECEx certification?

No. ATEX and IECEx are not listed; the unit is intended for general-purpose and marine (DNV GL) environments, not hazardous locations.

MPN
6EP1323-2BA00