Specifications

6EP1333-1LB00 — Electrical – Output
ParameterValue
Rated output voltage (DC)24 V
Rated current5 A
Rated current range0 ... 5 A; +45 ... +60 °C: Derating 2%/K
Output power at rated voltage/current (typ.)17 W
Output voltage characteristicControlled, isolated DC voltage
Output 1 rated voltage (DC)24 V
Output voltage adjustableYes
6EP1333-1LB00 — Electrical – Input & Efficiency
ParameterValue
Supplied active power (typ.)120 W
Efficiency86 %
Power supply network type1-phase AC
Maximum3.5 mA
6EP1333-1LB00 — Protection & Isolation
ParameterValue
Ingress protection (IP) ratingIP20
Protection classClass I
Short-circuit proof outputYes
Short-circuit protection designConstant current characteristic
Galvanic isolation input/outputYes
Galvanic isolation (SELV / standards)Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
6EP1333-1LB00 — Connections
ParameterValue
Electrical connection typescrew-type terminals
Input terminalsL, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
Output terminals+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
6EP1333-1LB00 — Mechanical
ParameterValue
Mounting methodSnaps onto DIN rail EN 60715 35x7.5/15
Enclosure width50 mm
Enclosure height125 mm
Enclosure depth120 mm
Side-by-side mountableYes
Mounting clearance, left0 mm
Mounting clearance, right0 mm
Mounting clearance, top50 mm
Mounting clearance, bottom50 mm
6EP1333-1LB00 — Environmental
ParameterValue
Operating temperature range0 ... 60 °C; with natural convection
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Climatic class (IEC 60721)Climate class 3K3, 5 … 95% no condensation
Current limitation of inrush current at 25 °C maximum32 A
6EP1333-1LB00 — Approvals & EMC
ParameterValue
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
CSA approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
NEC Class 2No
ATEX approvalNo
IECEx approvalNo
UL HazLoc approvalNo
cCSAus Class I Div 2 (hazardous loc.)No
EAC approvalYes
EMC – emission standardEN 55022 Class A
EMC – immunity standardEN 61000-6-2
6EP1333-1LB00 — Reliability & Features
ParameterValue
MTBF at 40 °C3 076 166 h
Equipment bridgingYes
Status indicators / displayGreen LED for 24 V OK
6EP1333-1LB00 — Electrical
ParameterValue
Adjustable Output Voltage22.8 ... 26.4 V

Product details

The Siemens 6EP1333-1LB00 is a SITOP modular power supply delivering a rated 5 A at safety extra-low voltage (SELV) output, per EN 60950-1 and EN 50178. It accepts dual-range AC input — 120 V (93–132 V) or 230 V (187–264 V) — selectable via a front-panel switch, and handles line frequencies from 47 to 63 Hz. The output is rated continuously at 5 A over 0–60 °C with natural convection; above 45 °C, derate at 2%/K. This unit snaps onto a standard DIN rail (EN 60715 35×7.5/15) and is IP20 rated, so it belongs inside a control cabinet — not in a washdown or outdoor location. The output terminals accept 0.5–2.5 mm² stranded or solid wire; input terminals are similarly sized, with L, N, and PE each on a dedicated screw clamp.

Installation notes

Mounting requires 50 mm clearance above and below the unit for convection airflow; left and right sides can be flush (0 mm clearance). The internal fuse is a T 3.15 A/250 V (not user-accessible). Siemens recommends a 6 A characteristic C miniature circuit breaker in the feeder. Off-state leakage is typically 0.4 mA, maximum 3.5 mA — negligible for most control circuits, but worth noting if you're feeding sensitive electronics that share a residual-current device.

Frequently asked questions

What approvals does 6EP1333-1LB00 carry?

CE, cULus (UL 508, CSA C22.2 No. 107.1, File E197259), and EAC. No ATEX, IECEx, DNV GL, FM, or UL hazloc.

What is the output voltage of 6EP1333-1LB00?

The output is SELV (safety extra-low voltage) per EN 60950-1 and EN 50178, set by a front-panel selector switch. The exact voltage depends on the switch setting — the datasheet covers the range.

What clearance is needed around 6EP1333-1LB00?

50 mm above and below for convection cooling; 0 mm left and right. Mount on DIN rail EN 60715 35×7.5/15.

MPN
6EP1333-1LB00