Skip to main content
Siemens 6EP1352-1SH03 — DIN Rail Power Supplies

Siemens 6EP1352-1SH03

MPN6EP1352-1SH03

********* spare part ********** LOGO!POWER 15 V/4 A stabilized power supply input: 100-240 V AC 110-300 V DC output: 15 V DC/4 A

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

6EP1352-1SH03 — Electrical – Output
ParameterValue
Rated output voltage (DC)15 V
Rated current4 A
Rated current range0 ... 4 A; +55 ... +70 °C: Derating 2%/K
Output power at rated voltage/current (typ.)11 W
Output voltage characteristicControlled, isolated DC voltage
Output 1 rated voltage (DC)15 V
Output voltage adjustableYes
6EP1352-1SH03 — Electrical – Input & Efficiency
ParameterValue
Supplied active power (typ.)50 W
Efficiency85 %
Power supply network type1-phase AC or DC
Maximum7 A
6EP1352-1SH03 — Protection & Isolation
ParameterValue
Ingress protection (IP) ratingIP20
Protection classClass II (without protective conductor)
Short-circuit proof outputYes
Short-circuit protection designConstant current characteristic
Galvanic isolation input/outputYes
Galvanic isolation (SELV / standards)Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
6EP1352-1SH03 — Connections
ParameterValue
Electrical connection typescrew-type terminals
Input terminalsL, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded
Output terminals+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
6EP1352-1SH03 — Mechanical
ParameterValue
Mounting methodSnaps onto DIN rail EN 60715 35x7.5/15
Enclosure width72 mm
Enclosure height90 mm
Enclosure depth52.6 mm
Side-by-side mountableYes
Mounting clearance, left0 mm
Mounting clearance, right0 mm
Mounting clearance, top20 mm
Mounting clearance, bottom20 mm
6EP1352-1SH03 — Environmental
ParameterValue
Operating temperature range-20 ... +70 °C; with natural convection
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Climatic class (IEC 60721)Climate class 3K3, 5 … 95% no condensation
Current limitation of inrush current at 25 °C maximum55 A
6EP1352-1SH03 — Approvals & EMC
ParameterValue
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310)
CSA approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310)
NEC Class 2Yes
ATEX approvalNo
IECEx approvalNo
UL HazLoc approvalNo
cCSAus Class I Div 2 (hazardous loc.)No
EAC approvalYes
Shipbuilding approvalABS, GL
EMC – emission standardEN 55022 Class B
EMC – immunity standardEN 61000-6-2
6EP1352-1SH03 — Reliability & Features
ParameterValue
MTBF at 40 °C3 800 981 h
Equipment bridgingYes
Status indicators / displayGreen LED for output voltage OK
6EP1352-1SH03 — Electrical
ParameterValue
Adjustable Output Voltage10.5 ... 16.1 V
MPN
6EP1352-1SH03