Skip to main content
Siemens 6EP1961-2BA41 — DIN Rail Power Supplies

Siemens 6EP1961-2BA41 Buffer Module, 4 Outputs, 22-30 VDC, D

MPN6EP1961-2BA41
Active

Siemens SITOP buffer module, 6EP1961-2BA41, 4 outputs, 22-30 VDC input, 99% efficiency, DIN rail EN 60715 mount, IP20.

$95.25Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6EP1961-2BA41 — Electrical – Output
ParameterValue
Output voltage characteristiccontrolled DC voltage
6EP1961-2BA41 — Electrical – Input & Efficiency
ParameterValue
Efficiency99 %
Power supply network typeControlled DC voltage
6EP1961-2BA41 — Protection & Isolation
ParameterValue
Ingress protection (IP) ratingIP20
Protection classClass III
6EP1961-2BA41 — Connections
ParameterValue
Electrical connection typescrew-type terminals
Input terminals+24 V: 2 screw terminals for 0.5 ... 16 mm²; 0 V: 2 screw terminals for 0.5 ... 4 mm²
Output terminalsOutput 1 ... 4: 1 screw terminal each for 0.5 ... 4 mm²
6EP1961-2BA41 — Mechanical
ParameterValue
Mounting methodSnaps onto DIN rail EN 60715 35x7.5/15
Enclosure width72 mm
Enclosure height80 mm
Enclosure depth72 mm
Mounting clearance, left0 mm
Mounting clearance, right0 mm
Mounting clearance, top50 mm
Mounting clearance, bottom50 mm
6EP1961-2BA41 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; with natural convection
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Climatic class (IEC 60721)climate class 3K3, 5 … 95% without condensation
6EP1961-2BA41 — Approvals & EMC
ParameterValue
CE markingYes
UL approvalYes; UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259
ATEX approvalNo
IECEx approvalNo
EAC approvalYes
Shipbuilding approvalDNV GL, ABS
EMC – emission standardEN 55022 Class B
EMC – immunity standardEN 61000-6-2
6EP1961-2BA41 — Reliability & Features
ParameterValue
MTBF at 40 °C540 979 h
Status indicators / displayThree-color LED per output: green LED for "Output switched through"; yellow LED for "Output switched off manually"; red LED for "Output switched off due to overcurrent"

Product details

The Siemens 6EP1961-2BA41 is a SITOP buffer module that bridges brief mains dips by delivering a controlled DC voltage at its four outputs, calculated as Vin minus approximately 0.2 V. It accepts a 22 to 30 V DC input and holds the output stable during interruptions, switching off after roughly 5 seconds at 1.0 to 1.5 times the set current, or after a typical 100 ms under a current limitation of 1.5 times the set value. This makes it a fit for keeping control logic or DC bus-powered devices alive through short supply glitches.

Snaps onto DIN rail EN 60715 35x7.5/15, occupying a 72 mm wide enclosure that stands 80 mm tall and 72 mm deep. Input side uses screw terminals accepting 0.5 to 16 mm² for the +24 V and 0.5 to 4 mm² for the 0 V return; each of the four outputs gets its own screw terminal for 0.5 to 4 mm². A separate screw terminal handles the signaling contact, and another handles the remote reset input.

Frequently asked questions

What compliance documentation does this module carry?

It carries CE marking, UL recognition (UL 2367), cULus listing (UL 508, CSA C22.2 No. 107.1), EAC approval, and shipbuilding approvals from DNV GL and ABS. Safety design follows EN 60950-1 and EN 50178.

What is the input voltage range and how does the output behave?

Input range is 22 to 30 V DC. The output is a controlled DC voltage equal to Vin minus approximately 0.2 V. Overcurrent protection trips after roughly 5 seconds at 1.0 to 1.5 times set current, and a fast current limitation shuts down after typical 100 ms at 1.5 times set value.

Can this module be used in marine or shipboard applications?

Yes, it holds DNV GL and ABS shipbuilding approvals, making it suitable for marine panel installations.