Skip to main content
Siemens 6EP3324-7SB00-3AX0 — DIN Rail Power Supplies

Siemens 6EP3324-7SB00-3AX0 Power Supply, 12 A, 85-275 VDC

MPN6EP3324-7SB00-3AX0
Active

Siemens SITOP PSU6200 power supply, 6EP3324-7SB00-3AX0, 12 A rated, 85-275 VDC / 120-240 VAC input, DIN-rail mount, cULus listed.

$156.21 – $464.67Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6EP3324-7SB00-3AX0 — Electrical – Output
ParameterValue
Rated output voltage (DC)12 V
Rated current12 A
Rated current range0 ... 12 A; 14.4 A up to +45°C; +60 ... +70 °C: Derating 3%/K
Output power at rated voltage/current (typ.)17 W
Output voltage characteristicControlled, isolated DC voltage
Output 1 rated voltage (DC)12 V
Output voltage adjustableYes
6EP3324-7SB00-3AX0 — Electrical – Input & Efficiency
ParameterValue
Supplied active power (typ.)144 W
Efficiency89.3 %
Power supply network type1-phase AC or DC
Maximum3.5 mA
6EP3324-7SB00-3AX0 — Protection & Isolation
ParameterValue
Ingress protection (IP) ratingIP20
Protection classClass I
Short-circuit proof outputYes
Short-circuit protection designShutdown and periodic restart attempts
Galvanic isolation input/outputYes
Galvanic isolation (SELV / standards)Safety extra low output voltage Vout according to EN 60950-1
6EP3324-7SB00-3AX0 — Connections
ParameterValue
Electrical connection typePush-in terminals
Input terminalsL1/+, L2/N/-, PE:PushIn for 0.5 ... 4 mm² single-core/finely stranded
Output terminals+1, +2, -1, -2, -3: PushIn for 0.5 ... 2.5 mm²
6EP3324-7SB00-3AX0 — Mechanical
ParameterValue
Mounting methodSnaps onto DIN rail EN 60715 35x7.5/15
Enclosure width45 mm
Enclosure height135 mm
Enclosure depth125 mm
Side-by-side mountableYes
Mounting clearance, left0 mm
Mounting clearance, right0 mm
Mounting clearance, top45 mm
Mounting clearance, bottom45 mm
6EP3324-7SB00-3AX0 — Environmental
ParameterValue
Operating temperature range-30 ... +70 °C; with natural convection a monotonically increasing start-up from -25 °C, safe start-up from -40 °C
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Climatic class (IEC 60721)Climate class 3K3, 5 … 95% no condensation
Current limitation of inrush current at 25 °C maximum6 A
6EP3324-7SB00-3AX0 — Approvals & EMC
ParameterValue
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
CSA approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
NEC Class 2No
ATEX approvalNo
IECEx approvalNo
UL HazLoc approvalNo
cCSAus Class I Div 2 (hazardous loc.)No
EAC approvalYes
Shipbuilding approvalABS; in process: DNV
EMC – emission standardEN 55022 Class B
EMC – immunity standardEN 61000-6-2
6EP3324-7SB00-3AX0 — Reliability & Features
ParameterValue
Equipment bridgingYes; switchable characteristic
Status indicators / displayGreen LED for 24 V OK
6EP3324-7SB00-3AX0 — Electrical
ParameterValue
Adjustable Output Voltage12 ... 15.5 V

Product details

The Siemens 6EP3324-7SB00-3AX0 is a SITOP PSU6200 power supply delivering a rated output of 12 A, with a typical current of 14.4 A available up to +45 °C. Input accepts 85...275 VDC or 120...240 VAC at 47...63 Hz. The unit snaps onto a DIN rail EN 60715 35x7.5/15 and is IP20 rated for panel mounting.

Rated output is 12 A continuous across the full input range. Up to 14.4 A is permissible at ambient temperatures up to +45 °C; above +60 °C the output must be derated by 3 %/K down to +70 °C. This makes the unit suitable for enclosures with limited airflow — plan the thermal budget accordingly. The input can be fed from a DC source spanning 85...275 V or an AC source 120...240 V, 47...63 Hz. The wide DC range covers nominal 110 V and 220 V battery banks without additional conditioning.

Required free space above and below the unit is 45 mm; no side clearance is needed (0 mm left and right). This tight footprint fits standard 200 mm deep enclosures.

Input protection and wiring

Recommended upstream protection: circuit breaker 4 A characteristic C, 6 A characteristic B, or 10 A characteristic C; alternatively a Siemens 3RV2011-1EA10 (set to 4 A) or 3RV2711-1ED10 (UL 489). Input terminals /+, L2/N/-, and PE accept PushIn connections for 0.5...4 mm² single-core or finely stranded wire. Output terminals +1, +2, -1, -2, -3 accept PushIn for 0.5...2.5 mm².

Frequently asked questions

What compliance documentation is available?

The unit carries CE marking, cULus listing (UL 508, CSA C22.2 No. 107.1), cCSAus (CSA C22.2 No. 60950-1, UL 60950-1), and EAC approval. No ATEX, IECEx, or FM registration.

What is the required clearance around the unit?

45 mm clearance is needed above and below the unit; no side clearance is required (0 mm left and right).

MPN
6EP3324-7SB00-3AX0