Siemens 6EP3334-7SB00-3AX0 — DIN Rail Power Supplies

Siemens 6EP3334-7SB00-3AX0 Power Supply, 12 A, 85-275 VDC In

MPN6EP3334-7SB00-3AX0
Active

Siemens SITOP PSU6200, 6EP3334-7SB00-3AX0, 12 A output, 85-275 VDC input, IP20, DIN rail.

$132.08 – $388.04Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6EP3334-7SB00-3AX0 — Electrical – Output
ParameterValue
Rated output voltage (DC)24 V
Rated current10 A
Rated current range0 ... 10 A; 12 A up to +45°C; +60 ... +70 °C: Derating 3%/K
Output power at rated voltage/current (typ.)18 W
Output voltage characteristicControlled, isolated DC voltage
Output 1 rated voltage (DC)24 V
Output voltage adjustableYes
6EP3334-7SB00-3AX0 — Electrical – Input & Efficiency
ParameterValue
Supplied active power (typ.)240 W
Efficiency92.8 %
Power supply network type1-phase AC or DC
Maximum3.5 mA
6EP3334-7SB00-3AX0 — Protection & Isolation
ParameterValue
Ingress protection (IP) ratingIP20
Protection classClass I
Short-circuit proof outputYes
Short-circuit protection designShutdown and periodic restart attempts
Galvanic isolation input/outputYes
Galvanic isolation (SELV / standards)Safety extra low output voltage Vout according to EN 60950-1
6EP3334-7SB00-3AX0 — Connections
ParameterValue
Electrical connection typePush-in terminals
Input terminalsL1/+, L2/N/-, PE:PushIn for 0.5 ... 4 mm² single-core/finely stranded
Output terminals+1, +2, -1, -2, -3: PushIn for 0.5 ... 2.5 mm²
6EP3334-7SB00-3AX0 — Mechanical
ParameterValue
Mounting methodSnaps onto DIN rail EN 60715 35x7.5/15
Enclosure width45 mm
Enclosure height135 mm
Enclosure depth125 mm
Side-by-side mountableYes
Mounting clearance, left0 mm
Mounting clearance, right0 mm
Mounting clearance, top45 mm
Mounting clearance, bottom45 mm
6EP3334-7SB00-3AX0 — Environmental
ParameterValue
Operating temperature range-30 ... +70 °C; with natural convection a monotonically increasing start-up from -25 °C, safe start-up from -40 °C
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Climatic class (IEC 60721)Climate class 3K3, 5 … 95% no condensation
Current limitation of inrush current at 25 °C maximum6 A
6EP3334-7SB00-3AX0 — Approvals & EMC
ParameterValue
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
CSA approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
NEC Class 2No
ATEX approvalNo
IECEx approvalNo
UL HazLoc approvalNo
cCSAus Class I Div 2 (hazardous loc.)No
EAC approvalYes
Shipbuilding approvalABS; in process: DNV
EMC – emission standardEN 55022 Class B
EMC – immunity standardEN 61000-6-2
6EP3334-7SB00-3AX0 — Reliability & Features
ParameterValue
Equipment bridgingYes; switchable characteristic
Status indicators / displayGreen LED for 24 V OK
6EP3334-7SB00-3AX0 — Electrical
ParameterValue
Adjustable Output Voltage24 ... 28 V

Product details

The Siemens 6EP3334-7SB00-3AX0 is a SITOP PSU6200 power supply delivering a rated 12 A output, with a rated range of 0-10 A continuous and 12 A up to +45°C. Above +60°C, derate by 3% per Kelvin up to +70°C — so at +65°C you're looking at roughly 10.2 A available. It accepts 85-275 VDC input, making it usable on DC bus systems or battery-backed installations without an AC feed.

The 12 A headline number is the short-term peak at moderate ambient — the real continuous rating is 10 A unless you keep the cabinet below 45°C. That derating curve matters for an enclosed panel with other heat sources. The 85-275 VDC input range means this unit can sit on a 110 VDC or 220 VDC plant battery bank without an intermediate converter. Galvanic isolation is SELV per EN 60950-1, so the output is safe to touch and suitable for feeding control circuits directly.

Mounting is snap-on DIN rail — no screws, no bracket. The input side uses PushIn terminals accepting 0.5-4 mm² single-core or finely stranded wire. Output side uses PushIn for 0.5-2.5 mm². That means no tool needed for termination, just strip and push. The recommended upstream protection is a circuit breaker 4 A char C / 6 A char B up to 10 A char C, or a 3RV2011-1EA10 set at 4 A.

Frequently asked questions

What compliance documentation does this power supply carry?

It carries UL 508 and CSA C22.2 No. 107.1 listing (File E197259), cCSAus to UL 60950-1 and CSA C22.2 No. 60950-1, CE marking, and EAC approval.

What's the real-world continuous current I can expect at 50°C ambient?

At 50°C you're within the 0-10 A rated range — no derating needed. The 12 A peak only applies up to +45°C. Above 60°C, derate 3% per Kelvin, so at 65°C expect roughly 10.2 A available.

Can this run on a 110 VDC battery bank?

Yes. The DC input range is 85-275 V, so it covers nominal 110 VDC and 220 VDC systems without issue.

MPN
6EP3334-7SB00-3AX0