Skip to main content
Siemens 6EP4134-0GL00-0AY0 — Power Supplies

Siemens 6EP4134-0GL00-0AY0

MPN6EP4134-0GL00-0AY0

SITOP UPS1100 EX battery module with maintenance- free closed lead batteries for SITOP DC UPS Module 24 V DC 7 Ah

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6EP4134-0GL00-0AY0 key specifications
ParameterValue
Type of electrical connectionscrew-type terminals
Output voltage at DC rated value24 V
Charging current maximum1.75 A
Output current rated value40 A
Design of Short-Circuit protectionBattery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse + support)
For power supply unit1 screw terminal each for 0.5 ... 16 mm² for + BAT and - BAT
Depth of the enclosure110 mm
Width of the enclosure186 mm
Height of the enclosure186 mm
Wall mountingYes
Mounting height201 mm
S7 rail mountingNo
6EP4134-0GL00-0AY0 — By ambient temperature
ParameterValue
At 20 °C typical4 a
At 30 °C typical2 a
At 40 °C typical1 a
At 50 °C typical0.5 a
At 0 °C recommended28 V
At 10 °C recommended27.8 V
At 20 °C recommended27.3 V
At 30 °C recommended26.8 V
At 40 °C recommended26.6 V
At 50 °C recommended26.3 V
At -10 °C recommended28 V

All specifications

6EP4134-0GL00-0AY0 additional specifications
ParameterValue
Installation width186 mm
Standard rail mountingNo
Ambient temperature during storageAlong with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.
CE markingYes
UL approvalNo
CSA approvalNo
Shipbuilding approvalavailable soon
Top15 mm
ATEXYes
Left0 mm
IECExYes
Right0 mm
Bottom0 mm
DNV GLNo
Typicalcapacity falls to 80 % of original capacity (according to EUROBAT)
During storage-20 ... +40 °C
Number of cells12
Battery capacity7 A·h
During operation-15 ... +50 °C
During transport-20 ... +50 °C
Mountingcan be screwed onto flat surface (keyhole mounting for hooking in to M4 screws)
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Operating data noteFor storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.
Protection class IPIP20
Product component includedAccessories pack with solid-state circuitry fuse 25 A
cCSAus, class 1, division 2No
Design of the overload protectionValve control
Operating resource protection classClass III
Display version for normal operationLED green: Battery OK; LED flashing green: Error or warning; OFF: No communication
For control circuit and status message1 screw terminal each for 0.14 ... 4 mm²
American bureau of shipping europe ltd.No
Relative temporary capacity loss at 20 °C in a month typical3 %
MPN