SITOP UPS1600 40 A Ethernet/ PROFINET uninterruptible power supply with Ethernet/ PROFINET interface / OPC UA server / web server input: 24 V DC output: 24 V DC/40 A *Ex approval no longer available*

$341.63Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6EP4137-3AB00-2AY0 — Electrical – Output
ParameterValue
Rated current40 A
Output power at rated voltage/current (typ.)17 W
6EP4137-3AB00-2AY0 — Electrical – Input & Efficiency
ParameterValue
Supplied active power (typ.)960 W
6EP4137-3AB00-2AY0 — Protection & Isolation
ParameterValue
Ingress protection (IP) ratingIP20
Protection classClass III
Short-circuit proof outputYes
Short-circuit protection designLimitation to 3 x I rated for 30 ms/min; through-conductivity for 1.5 x I rated for 5 sec/min
Galvanic isolation input/outputNo
6EP4137-3AB00-2AY0 — Connections
ParameterValue
Electrical connection typescrew-type terminals
Input terminals24 V DC: 2 screw terminals for 0.5 ... 16 mm²/20 ... 6 AWG
Output terminals24 V DC: 2 screw terminals for 0.5 ... 16 mm²/20 ... 6 AWG
6EP4137-3AB00-2AY0 — Mechanical
ParameterValue
Mounting methodSnaps onto DIN rail EN 60715 35x7.5/15
Enclosure width70 mm
Enclosure height139 mm
Enclosure depth150 mm
Side-by-side mountableYes
Mounting clearance, left0 mm
Mounting clearance, right0 mm
Mounting clearance, top50 mm
Mounting clearance, bottom50 mm
6EP4137-3AB00-2AY0 — Environmental
ParameterValue
Operating temperature range-25 ... +70 °C; with natural convection
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Climatic class (IEC 60721)Climate class 3K3, 5 … 95% no condensation
6EP4137-3AB00-2AY0 — Approvals & EMC
ParameterValue
CE markingYes
UL approvalYes
CSA approvalYes
ATEX approvalNo
cCSAus Class I Div 2 (hazardous loc.)No
EAC approvalYes
Shipbuilding approvalABS, DNV GL
EMC – emission standardEN 55022 Class B
EMC – immunity standardEN 61000-6-2
6EP4137-3AB00-2AY0 — Reliability & Features
ParameterValue
MTBF at 40 °C318 776 h
MPN
6EP4137-3AB00-2AY0