Siemens 6EP4143-8JB00-0XY0
MPN6EP4143-8JB00-0XY0
Active
SITOP BAT8600 LiFePO4 battery module for UPS8600 DC 48 V/264 Wh energy storage: mainten.-free lithium iron-phosph. batteries
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
| Parameter | Value |
|---|---|
| Type of electrical connection | Plug-in terminals with screwed connection |
| Output voltage at DC rated value | 48 V |
| Output current rated value | 20 A |
| Design of Short-Circuit protection | Blade-type fuse 40 A, 58 V DC |
| For power supply unit | +, -: 2 plug-in terminals with 1 screwed connection each for 0.2 ... 10 mm² |
| Number of Parallel-Switched equipment resources for increasing the power | 5 |
| Depth of the enclosure | 110 mm |
| Width of the enclosure | 322 mm |
| Height of the enclosure | 187 mm |
| Wall mounting | Yes |
| Mounting height | 207 mm |
| S7 rail mounting | No |
By ambient temperature4 ▾
| Parameter | Value |
|---|---|
| At 20 °C typical | 15 y |
| At 30 °C typical | 10 y |
| At 40 °C typical | 9 y |
| At 50 °C typical | 2 y |
All specifications+29 ▾
| Parameter | Value |
|---|---|
| Installation width | 322 mm |
| Standard rail mounting | No |
| Ambient temperature during storage | In addition to the storage temperature, additional factors, such as storage duration and charging status during storage, have a major impact on the potential service life. This means batteries should preferably be stored fully charged for short periods of time in a dry, cool and frost-proof (temperature range 0 to +20 °C) location. |
| UL approval | Yes |
| CSA approval | Yes |
| EAC approval | Yes |
| As approval for USA | cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) |
| Shipbuilding approval | ABS, DNV GL |
| Top | 20 mm |
| ATEX | No |
| Left | 0 mm |
| Right | 0 mm |
| Bottom | 0 mm |
| DNV GL | Yes |
| Typical | capacity falls to 80 % of original capacity (according to EUROBAT) |
| During storage | -40 ... +35 °C |
| During operation | -10 ... +50 °C |
| During transport | -40 ... +80 °C |
| Mounting | Keyhole mounting for hooking in to M4 screws |
| Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| Number of batteries | 4 |
| Operating data note | For storage, mounting and operation of batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. |
| Protection class IP | IP20 |
| Product component included | 2x blade-type fuse 40 A, 58 V DC |
| cCSAus, class 1, division 2 | No |
| Energy content of energy storage | 264 W·h |
| Design of the overload protection | Valve control |
| Operating resource protection class | Class III |
| American bureau of shipping europe ltd. | Yes |
MPN