6EP4347-7RC00-0AX0 — Electrical – Output
ParameterValue
Rated output voltage (DC)24 V
Rated current40 A
Output power at rated voltage/current (typ.)25 W
Output voltage characteristicControlled DC voltage
Output 1 rated voltage (DC)24 V
Output voltage adjustableNo
6EP4347-7RC00-0AX0 — Electrical – Input & Efficiency
ParameterValue
Efficiency97.5 %
Power supply network typeDC voltage
6EP4347-7RC00-0AX0 — Protection & Isolation
ParameterValue
Ingress protection (IP) ratingIP20
Protection classClass III
Galvanic isolation input/outputNo
6EP4347-7RC00-0AX0 — Connections
ParameterValue
Electrical connection typePush-in terminals
Input terminalsIn1, In2: each for 0.75 ... 16 mm²
Output terminalsOut1: 0.75 ... 16 mm²
6EP4347-7RC00-0AX0 — Mechanical
ParameterValue
Mounting methodSnaps onto DIN rail EN 60715 35x7.5/15
Enclosure width45 mm
Enclosure height135 mm
Enclosure depth125 mm
Side-by-side mountableYes
Mounting clearance, left0 mm
Mounting clearance, right0 mm
Mounting clearance, top45 mm
Mounting clearance, bottom45 mm
6EP4347-7RC00-0AX0 — Environmental
ParameterValue
Operating temperature range-30 ... +70 °C; with natural convection
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Climatic class (IEC 60721)Climate class 3K3, 5 … 95% no condensation
6EP4347-7RC00-0AX0 — Approvals & EMC
ParameterValue
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
CSA approvalYes; CSA C22.2 No. 62368-1
NEC Class 2No
ATEX approvalYes
IECEx approvalYes
UL HazLoc approvalNo
cCSAus Class I Div 2 (hazardous loc.)No
Shipbuilding approvalavailable soon
EMC – emission standardEN 61000-6-3
EMC – immunity standardEN 61000-6-2
6EP4347-7RC00-0AX0 — Reliability & Features
ParameterValue
MTBF at 40 °C6 100 000 h
Equipment bridgingNo
MPN