I/O mapping and slot constraints
The 6ES7132-6HD00-0BB0: Four relay outputs, each rated for up to 5 A continuous at 24 V DC. Switching frequency is limited to 2 Hz on resistive loads and 0.5 Hz inductive — do not use for fast pulse or PWM. No internal short-circuit protection on the outputs; plan external fusing per channel or per group. Address space uses 1 byte + 1 byte for QI (quality information); fits any ET 200SP base unit of type B0. Firmware V1.1, FW update possible via the backplane.
Mounting and wiring
Module width is 20 mm — account for slot count. Shielded cable runs up to 1 000 m; unshielded up to 200 m.